⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

60 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 60 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 0.69V (0.1%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 0.73V (0.11%)
Voltage at Load689.3 VLine Loss: 72.2 W
Max Power & Breaker71.71 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A7.41 V (1.07%)682.6 V12.23 V (1.77%)770.4 WDrop High
2.5 mm²24 A18 A4.45 V (0.64%)685.6 V7.34 V (1.06%)462.2 WDrop High
4 mm²32 A25 A2.78 V (0.4%)687.2 V4.59 V (0.66%)288.9 WDrop High
6 mm²41 A32 A1.85 V (0.27%)688.1 V3.06 V (0.44%)192.6 WDrop High
10 mm²57 A44 A1.11 V (0.16%)688.9 V1.83 V (0.27%)115.6 WDrop High
16 mm²76 A59 A0.69 V (0.1%)689.3 V1.15 V (0.17%)72.2 W✓ OK (≤3%)
25 mm²101 A78 A0.44 V (0.06%)689.6 V0.73 V (0.11%)46.2 W✓ OK (≤3%)
35 mm²125 A97 A0.32 V (0.05%)689.7 V0.52 V (0.08%)33.0 W✓ OK (≤3%)
50 mm²151 A118 A0.22 V (0.03%)689.8 V0.37 V (0.05%)23.1 W✓ OK (≤3%)
70 mm²192 A150 A0.16 V (0.02%)689.8 V0.26 V (0.04%)16.5 W✓ OK (≤3%)
95 mm²232 A181 A0.12 V (0.02%)689.9 V0.19 V (0.03%)12.2 W✓ OK (≤3%)
120 mm²269 A210 A0.09 V (0.01%)689.9 V0.15 V (0.02%)9.6 W✓ OK (≤3%)
150 mm²309 A241 A0.07 V (0.01%)689.9 V0.12 V (0.02%)7.7 W✓ OK (≤3%)
185 mm²353 A275 A0.06 V (0.01%)689.9 V0.1 V (0.01%)6.2 W✓ OK (≤3%)
240 mm²415 A324 A0.05 V (0.01%)690.0 V0.08 V (0.01%)4.8 W✓ OK (≤3%)
300 mm²477 A372 A0.04 V (0.01%)690.0 V0.06 V (0.01%)3.9 W✓ OK (≤3%)
400 mm²570 A445 A0.03 V (0.0%)690.0 V0.05 V (0.01%)2.9 W✓ OK (≤3%)

FAQ — 60 Amp Cable Size at 5 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 60A at 5 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 60A over 5m at 690V (voltage drop: 0.69V or 0.1%).

What is the power capacity of 60A at 690V?

At unity power factor, 60A at 690V supports 71.71 kW with a standard 60A circuit breaker.