600 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 600 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.23V (0.54%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.34V (1.77%)
Voltage at Load412.8 VLine Loss: 2311.2 W
Max Power & Breaker431.28 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1186.11 V (285.81%)0.0 V1956.52 V (471.45%)1232640.0 WDrop High
2.5 mm²24 A18 A711.67 V (171.49%)0.0 V1173.91 V (282.87%)739584.0 WDrop High
4 mm²32 A25 A444.79 V (107.18%)0.0 V733.7 V (176.79%)462240.0 WDrop High
6 mm²41 A32 A296.53 V (71.45%)118.5 V489.13 V (117.86%)308160.0 WDrop High
10 mm²57 A44 A177.92 V (42.87%)237.1 V293.48 V (70.72%)184896.0 WDrop High
16 mm²76 A59 A111.2 V (26.79%)303.8 V183.42 V (44.2%)115560.0 WDrop High
25 mm²101 A78 A71.17 V (17.15%)343.8 V117.39 V (28.29%)73958.4 WDrop High
35 mm²125 A97 A50.83 V (12.25%)364.2 V83.85 V (20.21%)52827.4 WDrop High
50 mm²151 A118 A35.58 V (8.57%)379.4 V58.7 V (14.14%)36979.2 WDrop High
70 mm²192 A150 A25.42 V (6.12%)389.6 V41.93 V (10.1%)26413.7 WDrop High
95 mm²232 A181 A18.73 V (4.51%)396.3 V30.89 V (7.44%)19462.7 WDrop High
120 mm²269 A210 A14.83 V (3.57%)400.2 V24.46 V (5.89%)15408.0 WDrop High
150 mm²309 A241 A11.86 V (2.86%)403.1 V19.57 V (4.71%)12326.4 WDrop High
185 mm²353 A275 A9.62 V (2.32%)405.4 V15.86 V (3.82%)9994.4 WDrop High
240 mm²415 A324 A7.41 V (1.79%)407.6 V12.23 V (2.95%)7704.0 WDrop High
300 mm²477 A372 A5.93 V (1.43%)409.1 V9.78 V (2.36%)6163.2 WDrop High
400 mm²570 A445 A4.45 V (1.07%)410.6 V7.34 V (1.77%)4622.4 WDrop High

FAQ — 600 Amp Cable Size at 80 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 600A at 80 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 600A over 80m at 415V (voltage drop: 2.23V or 0.54%).

What is the power capacity of 600A at 415V?

At unity power factor, 600A at 415V supports 431.28 kW with a standard 600A circuit breaker.