700 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.38V (1.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.24V (5.15%)
Voltage at Load23.6 VLine Loss: 262.1 W
Max Power & Breaker16.8 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A199.73 V (832.22%)0.0 V329.47 V (1372.78%)139813.3 WDrop High
2.5 mm²24 A18 A119.84 V (499.33%)0.0 V197.68 V (823.67%)83888.0 WDrop High
4 mm²32 A25 A74.9 V (312.08%)0.0 V123.55 V (514.79%)52430.0 WDrop High
6 mm²41 A32 A49.93 V (208.06%)0.0 V82.37 V (343.19%)34953.3 WDrop High
10 mm²57 A44 A29.96 V (124.83%)0.0 V49.42 V (205.92%)20972.0 WDrop High
16 mm²76 A59 A18.72 V (78.02%)5.3 V30.89 V (128.7%)13107.5 WDrop High
25 mm²101 A78 A11.98 V (49.93%)12.0 V19.77 V (82.37%)8388.8 WDrop High
35 mm²125 A97 A8.56 V (35.67%)15.4 V14.12 V (58.83%)5992.0 WDrop High
50 mm²151 A118 A5.99 V (24.97%)18.0 V9.88 V (41.18%)4194.4 WDrop High
70 mm²192 A150 A4.28 V (17.83%)19.7 V7.06 V (29.42%)2996.0 WDrop High
95 mm²232 A181 A3.15 V (13.14%)20.8 V5.2 V (21.68%)2207.6 WDrop High
120 mm²269 A210 A2.5 V (10.4%)21.5 V4.12 V (17.16%)1747.7 WDrop High
150 mm²309 A241 A2.0 V (8.32%)22.0 V3.29 V (13.73%)1398.1 WDrop High
185 mm²353 A275 A1.62 V (6.75%)22.4 V2.67 V (11.13%)1133.6 WDrop High
240 mm²415 A324 A1.25 V (5.2%)22.8 V2.06 V (8.58%)873.8 WDrop High
300 mm²477 A372 A1.0 V (4.16%)23.0 V1.65 V (6.86%)699.1 WDrop High
400 mm²570 A445 A0.75 V (3.12%)23.3 V1.24 V (5.15%)524.3 WDrop High

FAQ — 700 Amp Cable Size at 10 Meters (24V DC (Off-Grid Solar / Industrial Control))

What mm² cable size is required for 700A at 10 meters (24V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 10m at 24V (voltage drop: 0.38V or 1.56%).

What is the power capacity of 700A at 24V?

At unity power factor, 700A at 24V supports 16.8 kW with a standard 700A circuit breaker.