⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

700 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 5 m (16.4 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.16V (0.04%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 0.53V (0.13%)
Voltage at Load414.8 VLine Loss: 196.6 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A86.49 V (20.84%)328.5 V142.66 V (34.38%)104860.0 WDrop High
2.5 mm²24 A18 A51.89 V (12.5%)363.1 V85.6 V (20.63%)62916.0 WDrop High
4 mm²32 A25 A32.43 V (7.82%)382.6 V53.5 V (12.89%)39322.5 WDrop High
6 mm²41 A32 A21.62 V (5.21%)393.4 V35.67 V (8.59%)26215.0 WDrop High
10 mm²57 A44 A12.97 V (3.13%)402.0 V21.4 V (5.16%)15729.0 WDrop High
16 mm²76 A59 A8.11 V (1.95%)406.9 V13.37 V (3.22%)9830.6 WDrop High
25 mm²101 A78 A5.19 V (1.25%)409.8 V8.56 V (2.06%)6291.6 WDrop High
35 mm²125 A97 A3.71 V (0.89%)411.3 V6.11 V (1.47%)4494.0 WDrop High
50 mm²151 A118 A2.59 V (0.63%)412.4 V4.28 V (1.03%)3145.8 WDrop High
70 mm²192 A150 A1.85 V (0.45%)413.1 V3.06 V (0.74%)2247.0 WDrop High
95 mm²232 A181 A1.37 V (0.33%)413.6 V2.25 V (0.54%)1655.7 WDrop High
120 mm²269 A210 A1.08 V (0.26%)413.9 V1.78 V (0.43%)1310.8 WDrop High
150 mm²309 A241 A0.86 V (0.21%)414.1 V1.43 V (0.34%)1048.6 WDrop High
185 mm²353 A275 A0.7 V (0.17%)414.3 V1.16 V (0.28%)850.2 WDrop High
240 mm²415 A324 A0.54 V (0.13%)414.5 V0.89 V (0.21%)655.4 WDrop High
300 mm²477 A372 A0.43 V (0.1%)414.6 V0.71 V (0.17%)524.3 WDrop High
400 mm²570 A445 A0.32 V (0.08%)414.7 V0.53 V (0.13%)393.2 WDrop High

FAQ — 700 Amp Cable Size at 5 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 5 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 5m at 415V (voltage drop: 0.16V or 0.04%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.