700 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.65V (0.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.14V (0.52%)
Voltage at Load414.4 VLine Loss: 786.5 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A345.95 V (83.36%)69.1 V570.65 V (137.51%)419440.0 WDrop High
2.5 mm²24 A18 A207.57 V (50.02%)207.4 V342.39 V (82.5%)251664.0 WDrop High
4 mm²32 A25 A129.73 V (31.26%)285.3 V213.99 V (51.57%)157290.0 WDrop High
6 mm²41 A32 A86.49 V (20.84%)328.5 V142.66 V (34.38%)104860.0 WDrop High
10 mm²57 A44 A51.89 V (12.5%)363.1 V85.6 V (20.63%)62916.0 WDrop High
16 mm²76 A59 A32.43 V (7.82%)382.6 V53.5 V (12.89%)39322.5 WDrop High
25 mm²101 A78 A20.76 V (5.0%)394.2 V34.24 V (8.25%)25166.4 WDrop High
35 mm²125 A97 A14.83 V (3.57%)400.2 V24.46 V (5.89%)17976.0 WDrop High
50 mm²151 A118 A10.38 V (2.5%)404.6 V17.12 V (4.13%)12583.2 WDrop High
70 mm²192 A150 A7.41 V (1.79%)407.6 V12.23 V (2.95%)8988.0 WDrop High
95 mm²232 A181 A5.46 V (1.32%)409.5 V9.01 V (2.17%)6622.7 WDrop High
120 mm²269 A210 A4.32 V (1.04%)410.7 V7.13 V (1.72%)5243.0 WDrop High
150 mm²309 A241 A3.46 V (0.83%)411.5 V5.71 V (1.38%)4194.4 WDrop High
185 mm²353 A275 A2.8 V (0.68%)412.2 V4.63 V (1.11%)3400.9 WDrop High
240 mm²415 A324 A2.16 V (0.52%)412.8 V3.57 V (0.86%)2621.5 WDrop High
300 mm²477 A372 A1.73 V (0.42%)413.3 V2.85 V (0.69%)2097.2 WDrop High
400 mm²570 A445 A1.3 V (0.31%)413.7 V2.14 V (0.52%)1572.9 WDrop High

FAQ — 700 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 20m at 415V (voltage drop: 0.65V or 0.15%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.