700 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 50 m (164.0 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.62V (0.39%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.35V (1.29%)
Voltage at Load413.4 VLine Loss: 1966.1 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 50m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A864.87 V (208.4%)0.0 V1426.63 V (343.77%)1048600.0 WDrop High
2.5 mm²24 A18 A518.92 V (125.04%)0.0 V855.98 V (206.26%)629160.0 WDrop High
4 mm²32 A25 A324.33 V (78.15%)90.7 V534.99 V (128.91%)393225.0 WDrop High
6 mm²41 A32 A216.22 V (52.1%)198.8 V356.66 V (85.94%)262150.0 WDrop High
10 mm²57 A44 A129.73 V (31.26%)285.3 V213.99 V (51.57%)157290.0 WDrop High
16 mm²76 A59 A81.08 V (19.54%)333.9 V133.75 V (32.23%)98306.2 WDrop High
25 mm²101 A78 A51.89 V (12.5%)363.1 V85.6 V (20.63%)62916.0 WDrop High
35 mm²125 A97 A37.07 V (8.93%)377.9 V61.14 V (14.73%)44940.0 WDrop High
50 mm²151 A118 A25.95 V (6.25%)389.1 V42.8 V (10.31%)31458.0 WDrop High
70 mm²192 A150 A18.53 V (4.47%)396.5 V30.57 V (7.37%)22470.0 WDrop High
95 mm²232 A181 A13.66 V (3.29%)401.3 V22.53 V (5.43%)16556.8 WDrop High
120 mm²269 A210 A10.81 V (2.61%)404.2 V17.83 V (4.3%)13107.5 WDrop High
150 mm²309 A241 A8.65 V (2.08%)406.4 V14.27 V (3.44%)10486.0 WDrop High
185 mm²353 A275 A7.01 V (1.69%)408.0 V11.57 V (2.79%)8502.2 WDrop High
240 mm²415 A324 A5.41 V (1.3%)409.6 V8.92 V (2.15%)6553.7 WDrop High
300 mm²477 A372 A4.32 V (1.04%)410.7 V7.13 V (1.72%)5243.0 WDrop High
400 mm²570 A445 A3.24 V (0.78%)411.8 V5.35 V (1.29%)3932.2 WDrop High

FAQ — 700 Amp Cable Size at 50 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 50 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 50m at 415V (voltage drop: 1.62V or 0.39%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.