⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

700 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.27V (0.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.49V (1.8%)
Voltage at Load412.7 VLine Loss: 2752.6 W
Max Power & Breaker503.16 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1210.82 V (291.76%)0.0 V1997.29 V (481.27%)1468040.0 WDrop High
2.5 mm²24 A18 A726.49 V (175.06%)0.0 V1198.37 V (288.76%)880824.0 WDrop High
4 mm²32 A25 A454.06 V (109.41%)0.0 V748.98 V (180.48%)550515.0 WDrop High
6 mm²41 A32 A302.7 V (72.94%)112.3 V499.32 V (120.32%)367010.0 WDrop High
10 mm²57 A44 A181.62 V (43.76%)233.4 V299.59 V (72.19%)220206.0 WDrop High
16 mm²76 A59 A113.51 V (27.35%)301.5 V187.25 V (45.12%)137628.8 WDrop High
25 mm²101 A78 A72.65 V (17.51%)342.4 V119.84 V (28.88%)88082.4 WDrop High
35 mm²125 A97 A51.89 V (12.5%)363.1 V85.6 V (20.63%)62916.0 WDrop High
50 mm²151 A118 A36.32 V (8.75%)378.7 V59.92 V (14.44%)44041.2 WDrop High
70 mm²192 A150 A25.95 V (6.25%)389.1 V42.8 V (10.31%)31458.0 WDrop High
95 mm²232 A181 A19.12 V (4.61%)395.9 V31.54 V (7.6%)23179.6 WDrop High
120 mm²269 A210 A15.14 V (3.65%)399.9 V24.97 V (6.02%)18350.5 WDrop High
150 mm²309 A241 A12.11 V (2.92%)402.9 V19.97 V (4.81%)14680.4 WDrop High
185 mm²353 A275 A9.82 V (2.37%)405.2 V16.19 V (3.9%)11903.0 WDrop High
240 mm²415 A324 A7.57 V (1.82%)407.4 V12.48 V (3.01%)9175.2 WDrop High
300 mm²477 A372 A6.05 V (1.46%)408.9 V9.99 V (2.41%)7340.2 WDrop High
400 mm²570 A445 A4.54 V (1.09%)410.5 V7.49 V (1.8%)5505.2 WDrop High

FAQ — 700 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 700A at 70 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 700A over 70m at 415V (voltage drop: 2.27V or 0.55%).

What is the power capacity of 700A at 415V?

At unity power factor, 700A at 415V supports 503.16 kW with a standard 700A circuit breaker.