⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

700 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 700 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)5× 400 mm²Drop: 1.2V (2.5%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.88V (20.59%)
Voltage at Load46.8 VLine Loss: 838.9 W
Max Power & Breaker33.6 kW700A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 700A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1597.87 V (3328.89%)0.0 V2635.73 V (5491.11%)1118506.7 WDrop High
2.5 mm²24 A18 A958.72 V (1997.33%)0.0 V1581.44 V (3294.67%)671104.0 WDrop High
4 mm²32 A25 A599.2 V (1248.33%)0.0 V988.4 V (2059.17%)419440.0 WDrop High
6 mm²41 A32 A399.47 V (832.22%)0.0 V658.93 V (1372.78%)279626.7 WDrop High
10 mm²57 A44 A239.68 V (499.33%)0.0 V395.36 V (823.67%)167776.0 WDrop High
16 mm²76 A59 A149.8 V (312.08%)0.0 V247.1 V (514.79%)104860.0 WDrop High
25 mm²101 A78 A95.87 V (199.73%)0.0 V158.14 V (329.47%)67110.4 WDrop High
35 mm²125 A97 A68.48 V (142.67%)0.0 V112.96 V (235.33%)47936.0 WDrop High
50 mm²151 A118 A47.94 V (99.87%)0.1 V79.07 V (164.73%)33555.2 WDrop High
70 mm²192 A150 A34.24 V (71.33%)13.8 V56.48 V (117.67%)23968.0 WDrop High
95 mm²232 A181 A25.23 V (52.56%)22.8 V41.62 V (86.7%)17660.6 WDrop High
120 mm²269 A210 A19.97 V (41.61%)28.0 V32.95 V (68.64%)13981.3 WDrop High
150 mm²309 A241 A15.98 V (33.29%)32.0 V26.36 V (54.91%)11185.1 WDrop High
185 mm²353 A275 A12.96 V (26.99%)35.0 V21.37 V (44.52%)9069.0 WDrop High
240 mm²415 A324 A9.99 V (20.81%)38.0 V16.47 V (34.32%)6990.7 WDrop High
300 mm²477 A372 A7.99 V (16.64%)40.0 V13.18 V (27.46%)5592.5 WDrop High
400 mm²570 A445 A5.99 V (12.48%)42.0 V9.88 V (20.59%)4194.4 WDrop High

FAQ — 700 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 700A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 5× 400 mm² copper cable for 700A over 80m at 48V (voltage drop: 1.2V or 2.5%).

What is the power capacity of 700A at 48V?

At unity power factor, 700A at 48V supports 33.6 kW with a standard 700A circuit breaker.