750 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 750 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 13.9V (2.01%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 68.78V (9.97%)
Voltage at Load676.1 VLine Loss: 18056.2 W
Max Power & Breaker896.34 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 750A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11119.77 V (1611.56%)0.0 V18342.42 V (2658.32%)14445000.0 WDrop High
2.5 mm²24 A18 A6671.86 V (966.94%)0.0 V11005.45 V (1594.99%)8667000.0 WDrop High
4 mm²32 A25 A4169.91 V (604.34%)0.0 V6878.41 V (996.87%)5416875.0 WDrop High
6 mm²41 A32 A2779.94 V (402.89%)0.0 V4585.6 V (664.58%)3611250.0 WDrop High
10 mm²57 A44 A1667.96 V (241.73%)0.0 V2751.36 V (398.75%)2166750.0 WDrop High
16 mm²76 A59 A1042.48 V (151.08%)0.0 V1719.6 V (249.22%)1354218.8 WDrop High
25 mm²101 A78 A667.19 V (96.69%)22.8 V1100.55 V (159.5%)866700.0 WDrop High
35 mm²125 A97 A476.56 V (69.07%)213.4 V786.1 V (113.93%)619071.4 WDrop High
50 mm²151 A118 A333.59 V (48.35%)356.4 V550.27 V (79.75%)433350.0 WDrop High
70 mm²192 A150 A238.28 V (34.53%)451.7 V393.05 V (56.96%)309535.7 WDrop High
95 mm²232 A181 A175.58 V (25.45%)514.4 V289.62 V (41.97%)228078.9 WDrop High
120 mm²269 A210 A139.0 V (20.14%)551.0 V229.28 V (33.23%)180562.5 WDrop High
150 mm²309 A241 A111.2 V (16.12%)578.8 V183.42 V (26.58%)144450.0 WDrop High
185 mm²353 A275 A90.16 V (13.07%)599.8 V148.72 V (21.55%)117121.6 WDrop High
240 mm²415 A324 A69.5 V (10.07%)620.5 V114.64 V (16.61%)90281.2 WDrop High
300 mm²477 A372 A55.6 V (8.06%)634.4 V91.71 V (13.29%)72225.0 WDrop High
400 mm²570 A445 A41.7 V (6.04%)648.3 V68.78 V (9.97%)54168.7 WDrop High

FAQ — 750 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 750A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 750A over 600m at 690V (voltage drop: 13.9V or 2.01%).

What is the power capacity of 750A at 690V?

At unity power factor, 750A at 690V supports 896.34 kW with a standard 800A circuit breaker.