800 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.74V (0.18%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.45V (0.59%)
Voltage at Load414.3 VLine Loss: 1027.2 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A395.37 V (95.27%)19.6 V652.17 V (157.15%)547840.0 WDrop High
2.5 mm²24 A18 A237.22 V (57.16%)177.8 V391.3 V (94.29%)328704.0 WDrop High
4 mm²32 A25 A148.26 V (35.73%)266.7 V244.57 V (58.93%)205440.0 WDrop High
6 mm²41 A32 A98.84 V (23.82%)316.2 V163.04 V (39.29%)136960.0 WDrop High
10 mm²57 A44 A59.31 V (14.29%)355.7 V97.83 V (23.57%)82176.0 WDrop High
16 mm²76 A59 A37.07 V (8.93%)377.9 V61.14 V (14.73%)51360.0 WDrop High
25 mm²101 A78 A23.72 V (5.72%)391.3 V39.13 V (9.43%)32870.4 WDrop High
35 mm²125 A97 A16.94 V (4.08%)398.1 V27.95 V (6.74%)23478.9 WDrop High
50 mm²151 A118 A11.86 V (2.86%)403.1 V19.57 V (4.71%)16435.2 WDrop High
70 mm²192 A150 A8.47 V (2.04%)406.5 V13.98 V (3.37%)11739.4 WDrop High
95 mm²232 A181 A6.24 V (1.5%)408.8 V10.3 V (2.48%)8650.1 WDrop High
120 mm²269 A210 A4.94 V (1.19%)410.1 V8.15 V (1.96%)6848.0 WDrop High
150 mm²309 A241 A3.95 V (0.95%)411.0 V6.52 V (1.57%)5478.4 WDrop High
185 mm²353 A275 A3.21 V (0.77%)411.8 V5.29 V (1.27%)4441.9 WDrop High
240 mm²415 A324 A2.47 V (0.6%)412.5 V4.08 V (0.98%)3424.0 WDrop High
300 mm²477 A372 A1.98 V (0.48%)413.0 V3.26 V (0.79%)2739.2 WDrop High
400 mm²570 A445 A1.48 V (0.36%)413.5 V2.45 V (0.59%)2054.4 WDrop High

FAQ — 800 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 20m at 415V (voltage drop: 0.74V or 0.18%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.