800 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.67V (0.4%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.5V (1.33%)
Voltage at Load413.3 VLine Loss: 2311.2 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A889.58 V (214.36%)0.0 V1467.39 V (353.59%)1232640.0 WDrop High
2.5 mm²24 A18 A533.75 V (128.61%)0.0 V880.44 V (212.15%)739584.0 WDrop High
4 mm²32 A25 A333.59 V (80.38%)81.4 V550.27 V (132.6%)462240.0 WDrop High
6 mm²41 A32 A222.4 V (53.59%)192.6 V366.85 V (88.4%)308160.0 WDrop High
10 mm²57 A44 A133.44 V (32.15%)281.6 V220.11 V (53.04%)184896.0 WDrop High
16 mm²76 A59 A83.4 V (20.1%)331.6 V137.57 V (33.15%)115560.0 WDrop High
25 mm²101 A78 A53.37 V (12.86%)361.6 V88.04 V (21.22%)73958.4 WDrop High
35 mm²125 A97 A38.12 V (9.19%)376.9 V62.89 V (15.15%)52827.4 WDrop High
50 mm²151 A118 A26.69 V (6.43%)388.3 V44.02 V (10.61%)36979.2 WDrop High
70 mm²192 A150 A19.06 V (4.59%)395.9 V31.44 V (7.58%)26413.7 WDrop High
95 mm²232 A181 A14.05 V (3.38%)401.0 V23.17 V (5.58%)19462.7 WDrop High
120 mm²269 A210 A11.12 V (2.68%)403.9 V18.34 V (4.42%)15408.0 WDrop High
150 mm²309 A241 A8.9 V (2.14%)406.1 V14.67 V (3.54%)12326.4 WDrop High
185 mm²353 A275 A7.21 V (1.74%)407.8 V11.9 V (2.87%)9994.4 WDrop High
240 mm²415 A324 A5.56 V (1.34%)409.4 V9.17 V (2.21%)7704.0 WDrop High
300 mm²477 A372 A4.45 V (1.07%)410.6 V7.34 V (1.77%)6163.2 WDrop High
400 mm²570 A445 A3.34 V (0.8%)411.7 V5.5 V (1.33%)4622.4 WDrop High

FAQ — 800 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 45m at 415V (voltage drop: 1.67V or 0.4%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.