⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

800 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 250 m (820.2 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 9.27V (2.23%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 30.57V (7.37%)
Voltage at Load405.7 VLine Loss: 12840.0 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4942.12 V (1190.87%)0.0 V8152.19 V (1964.38%)6848000.0 WDrop High
2.5 mm²24 A18 A2965.27 V (714.52%)0.0 V4891.31 V (1178.63%)4108800.0 WDrop High
4 mm²32 A25 A1853.29 V (446.58%)0.0 V3057.07 V (736.64%)2568000.0 WDrop High
6 mm²41 A32 A1235.53 V (297.72%)0.0 V2038.05 V (491.1%)1712000.0 WDrop High
10 mm²57 A44 A741.32 V (178.63%)0.0 V1222.83 V (294.66%)1027200.0 WDrop High
16 mm²76 A59 A463.32 V (111.64%)0.0 V764.27 V (184.16%)642000.0 WDrop High
25 mm²101 A78 A296.53 V (71.45%)118.5 V489.13 V (117.86%)410880.0 WDrop High
35 mm²125 A97 A211.81 V (51.04%)203.2 V349.38 V (84.19%)293485.7 WDrop High
50 mm²151 A118 A148.26 V (35.73%)266.7 V244.57 V (58.93%)205440.0 WDrop High
70 mm²192 A150 A105.9 V (25.52%)309.1 V174.69 V (42.09%)146742.9 WDrop High
95 mm²232 A181 A78.03 V (18.8%)337.0 V128.72 V (31.02%)108126.3 WDrop High
120 mm²269 A210 A61.78 V (14.89%)353.2 V101.9 V (24.55%)85600.0 WDrop High
150 mm²309 A241 A49.42 V (11.91%)365.6 V81.52 V (19.64%)68480.0 WDrop High
185 mm²353 A275 A40.07 V (9.66%)374.9 V66.1 V (15.93%)55524.3 WDrop High
240 mm²415 A324 A30.89 V (7.44%)384.1 V50.95 V (12.28%)42800.0 WDrop High
300 mm²477 A372 A24.71 V (5.95%)390.3 V40.76 V (9.82%)34240.0 WDrop High
400 mm²570 A445 A18.53 V (4.47%)396.5 V30.57 V (7.37%)25680.0 WDrop High

FAQ — 800 Amp Cable Size at 250 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 250 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 250m at 415V (voltage drop: 9.27V or 2.23%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.