⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

800 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 11.12V (2.68%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 36.68V (8.84%)
Voltage at Load403.9 VLine Loss: 15408.0 W
Max Power & Breaker575.04 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A5930.54 V (1429.05%)0.0 V9782.62 V (2357.26%)8217600.0 WDrop High
2.5 mm²24 A18 A3558.33 V (857.43%)0.0 V5869.57 V (1414.36%)4930560.0 WDrop High
4 mm²32 A25 A2223.95 V (535.89%)0.0 V3668.48 V (883.97%)3081600.0 WDrop High
6 mm²41 A32 A1482.64 V (357.26%)0.0 V2445.66 V (589.31%)2054400.0 WDrop High
10 mm²57 A44 A889.58 V (214.36%)0.0 V1467.39 V (353.59%)1232640.0 WDrop High
16 mm²76 A59 A555.99 V (133.97%)0.0 V917.12 V (220.99%)770400.0 WDrop High
25 mm²101 A78 A355.83 V (85.74%)59.2 V586.96 V (141.44%)493056.0 WDrop High
35 mm²125 A97 A254.17 V (61.24%)160.8 V419.26 V (101.03%)352182.9 WDrop High
50 mm²151 A118 A177.92 V (42.87%)237.1 V293.48 V (70.72%)246528.0 WDrop High
70 mm²192 A150 A127.08 V (30.62%)287.9 V209.63 V (50.51%)176091.4 WDrop High
95 mm²232 A181 A93.64 V (22.56%)321.4 V154.46 V (37.22%)129751.6 WDrop High
120 mm²269 A210 A74.13 V (17.86%)340.9 V122.28 V (29.47%)102720.0 WDrop High
150 mm²309 A241 A59.31 V (14.29%)355.7 V97.83 V (23.57%)82176.0 WDrop High
185 mm²353 A275 A48.09 V (11.59%)366.9 V79.32 V (19.11%)66629.2 WDrop High
240 mm²415 A324 A37.07 V (8.93%)377.9 V61.14 V (14.73%)51360.0 WDrop High
300 mm²477 A372 A29.65 V (7.15%)385.3 V48.91 V (11.79%)41088.0 WDrop High
400 mm²570 A445 A22.24 V (5.36%)392.8 V36.68 V (8.84%)30816.0 WDrop High

FAQ — 800 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 800A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 800A over 300m at 415V (voltage drop: 11.12V or 2.68%).

What is the power capacity of 800A at 415V?

At unity power factor, 800A at 415V supports 575.04 kW with a standard 800A circuit breaker.