⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

800 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 800 A over 600 m (1968.5 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 14.83V (2.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 73.37V (10.63%)
Voltage at Load675.2 VLine Loss: 20544.0 W
Max Power & Breaker956.09 kW800A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 800A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A11861.08 V (1719.0%)0.0 V19565.25 V (2835.54%)16435200.0 WDrop High
2.5 mm²24 A18 A7116.65 V (1031.4%)0.0 V11739.15 V (1701.33%)9861120.0 WDrop High
4 mm²32 A25 A4447.91 V (644.62%)0.0 V7336.97 V (1063.33%)6163200.0 WDrop High
6 mm²41 A32 A2965.27 V (429.75%)0.0 V4891.31 V (708.89%)4108800.0 WDrop High
10 mm²57 A44 A1779.16 V (257.85%)0.0 V2934.79 V (425.33%)2465280.0 WDrop High
16 mm²76 A59 A1111.98 V (161.16%)0.0 V1834.24 V (265.83%)1540800.0 WDrop High
25 mm²101 A78 A711.67 V (103.14%)0.0 V1173.91 V (170.13%)986112.0 WDrop High
35 mm²125 A97 A508.33 V (73.67%)181.7 V838.51 V (121.52%)704365.7 WDrop High
50 mm²151 A118 A355.83 V (51.57%)334.2 V586.96 V (85.07%)493056.0 WDrop High
70 mm²192 A150 A254.17 V (36.84%)435.8 V419.26 V (60.76%)352182.9 WDrop High
95 mm²232 A181 A187.28 V (27.14%)502.7 V308.92 V (44.77%)259503.2 WDrop High
120 mm²269 A210 A148.26 V (21.49%)541.7 V244.57 V (35.44%)205440.0 WDrop High
150 mm²309 A241 A118.61 V (17.19%)571.4 V195.65 V (28.36%)164352.0 WDrop High
185 mm²353 A275 A96.17 V (13.94%)593.8 V158.64 V (22.99%)133258.4 WDrop High
240 mm²415 A324 A74.13 V (10.74%)615.9 V122.28 V (17.72%)102720.0 WDrop High
300 mm²477 A372 A59.31 V (8.59%)630.7 V97.83 V (14.18%)82176.0 WDrop High
400 mm²570 A445 A44.48 V (6.45%)645.5 V73.37 V (10.63%)61632.0 WDrop High

FAQ — 800 Amp Cable Size at 600 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 800A at 600 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 800A over 600m at 690V (voltage drop: 14.83V or 2.15%).

What is the power capacity of 800A at 690V?

At unity power factor, 800A at 690V supports 956.09 kW with a standard 800A circuit breaker.