⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

900 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 10 m (32.8 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.41V (0.1%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.38V (0.33%)
Voltage at Load414.6 VLine Loss: 650.0 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A222.4 V (53.59%)192.6 V366.85 V (88.4%)346680.0 WDrop High
2.5 mm²24 A18 A133.44 V (32.15%)281.6 V220.11 V (53.04%)208008.0 WDrop High
4 mm²32 A25 A83.4 V (20.1%)331.6 V137.57 V (33.15%)130005.0 WDrop High
6 mm²41 A32 A55.6 V (13.4%)359.4 V91.71 V (22.1%)86670.0 WDrop High
10 mm²57 A44 A33.36 V (8.04%)381.6 V55.03 V (13.26%)52002.0 WDrop High
16 mm²76 A59 A20.85 V (5.02%)394.2 V34.39 V (8.29%)32501.2 WDrop High
25 mm²101 A78 A13.34 V (3.22%)401.7 V22.01 V (5.3%)20800.8 WDrop High
35 mm²125 A97 A9.53 V (2.3%)405.5 V15.72 V (3.79%)14857.7 WDrop High
50 mm²151 A118 A6.67 V (1.61%)408.3 V11.01 V (2.65%)10400.4 WDrop High
70 mm²192 A150 A4.77 V (1.15%)410.2 V7.86 V (1.89%)7428.9 WDrop High
95 mm²232 A181 A3.51 V (0.85%)411.5 V5.79 V (1.4%)5473.9 WDrop High
120 mm²269 A210 A2.78 V (0.67%)412.2 V4.59 V (1.1%)4333.5 WDrop High
150 mm²309 A241 A2.22 V (0.54%)412.8 V3.67 V (0.88%)3466.8 WDrop High
185 mm²353 A275 A1.8 V (0.43%)413.2 V2.97 V (0.72%)2810.9 WDrop High
240 mm²415 A324 A1.39 V (0.33%)413.6 V2.29 V (0.55%)2166.8 WDrop High
300 mm²477 A372 A1.11 V (0.27%)413.9 V1.83 V (0.44%)1733.4 WDrop High
400 mm²570 A445 A0.83 V (0.2%)414.2 V1.38 V (0.33%)1300.0 WDrop High

FAQ — 900 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 10 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 10m at 415V (voltage drop: 0.41V or 0.1%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.