900 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))
IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 10 m (32.8 ft).
Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.41V (0.1%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 1.38V (0.33%)
Voltage at Load414.6 VLine Loss: 650.0 W
Max Power & Breaker646.92 kW1000A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 222.4 V (53.59%) | 192.6 V | 366.85 V (88.4%) | 346680.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 133.44 V (32.15%) | 281.6 V | 220.11 V (53.04%) | 208008.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 83.4 V (20.1%) | 331.6 V | 137.57 V (33.15%) | 130005.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 55.6 V (13.4%) | 359.4 V | 91.71 V (22.1%) | 86670.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 33.36 V (8.04%) | 381.6 V | 55.03 V (13.26%) | 52002.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 20.85 V (5.02%) | 394.2 V | 34.39 V (8.29%) | 32501.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 13.34 V (3.22%) | 401.7 V | 22.01 V (5.3%) | 20800.8 W | Drop High |
| 35 mm² | 125 A | 97 A | 9.53 V (2.3%) | 405.5 V | 15.72 V (3.79%) | 14857.7 W | Drop High |
| 50 mm² | 151 A | 118 A | 6.67 V (1.61%) | 408.3 V | 11.01 V (2.65%) | 10400.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 4.77 V (1.15%) | 410.2 V | 7.86 V (1.89%) | 7428.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 3.51 V (0.85%) | 411.5 V | 5.79 V (1.4%) | 5473.9 W | Drop High |
| 120 mm² | 269 A | 210 A | 2.78 V (0.67%) | 412.2 V | 4.59 V (1.1%) | 4333.5 W | Drop High |
| 150 mm² | 309 A | 241 A | 2.22 V (0.54%) | 412.8 V | 3.67 V (0.88%) | 3466.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 1.8 V (0.43%) | 413.2 V | 2.97 V (0.72%) | 2810.9 W | Drop High |
| 240 mm² | 415 A | 324 A | 1.39 V (0.33%) | 413.6 V | 2.29 V (0.55%) | 2166.8 W | Drop High |
| 300 mm² | 477 A | 372 A | 1.11 V (0.27%) | 413.9 V | 1.83 V (0.44%) | 1733.4 W | Drop High |
| 400 mm² | 570 A | 445 A | 0.83 V (0.2%) | 414.2 V | 1.38 V (0.33%) | 1300.0 W | Drop High |
FAQ — 900 Amp Cable Size at 10 Meters (415V Three-Phase (UK / Australia Industrial))
What mm² cable size is required for 900A at 10 meters (415V)?
According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 10m at 415V (voltage drop: 0.41V or 0.1%).
What is the power capacity of 900A at 415V?
At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.
Related Lengths & Currents (415V)
900A · 5m (415V)900A · 15m (415V)900A · 20m (415V)900A · 25m (415V)900A · 30m (415V)900A · 35m (415V)900A · 40m (415V)900A · 45m (415V)900A · 50m (415V)900A · 60m (415V)900A · 70m (415V)10A · 10m (415V)16A · 10m (415V)20A · 10m (415V)25A · 10m (415V)32A · 10m (415V)40A · 10m (415V)50A · 10m (415V)63A · 10m (415V)80A · 10m (415V)100A · 10m (415V)125A · 10m (415V)160A · 10m (415V)200A · 10m (415V)