⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

900 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 70 m (229.7 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.92V (0.7%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 9.63V (2.32%)
Voltage at Load412.1 VLine Loss: 4550.2 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 70m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1556.77 V (375.12%)0.0 V2567.94 V (618.78%)2426760.0 WDrop High
2.5 mm²24 A18 A934.06 V (225.07%)0.0 V1540.76 V (371.27%)1456056.0 WDrop High
4 mm²32 A25 A583.79 V (140.67%)0.0 V962.98 V (232.04%)910035.0 WDrop High
6 mm²41 A32 A389.19 V (93.78%)25.8 V641.98 V (154.7%)606690.0 WDrop High
10 mm²57 A44 A233.52 V (56.27%)181.5 V385.19 V (92.82%)364014.0 WDrop High
16 mm²76 A59 A145.95 V (35.17%)269.1 V240.74 V (58.01%)227508.8 WDrop High
25 mm²101 A78 A93.41 V (22.51%)321.6 V154.08 V (37.13%)145605.6 WDrop High
35 mm²125 A97 A66.72 V (16.08%)348.3 V110.05 V (26.52%)104004.0 WDrop High
50 mm²151 A118 A46.7 V (11.25%)368.3 V77.04 V (18.56%)72802.8 WDrop High
70 mm²192 A150 A33.36 V (8.04%)381.6 V55.03 V (13.26%)52002.0 WDrop High
95 mm²232 A181 A24.58 V (5.92%)390.4 V40.55 V (9.77%)38317.3 WDrop High
120 mm²269 A210 A19.46 V (4.69%)395.5 V32.1 V (7.73%)30334.5 WDrop High
150 mm²309 A241 A15.57 V (3.75%)399.4 V25.68 V (6.19%)24267.6 WDrop High
185 mm²353 A275 A12.62 V (3.04%)402.4 V20.82 V (5.02%)19676.4 WDrop High
240 mm²415 A324 A9.73 V (2.34%)405.3 V16.05 V (3.87%)15167.3 WDrop High
300 mm²477 A372 A7.78 V (1.88%)407.2 V12.84 V (3.09%)12133.8 WDrop High
400 mm²570 A445 A5.84 V (1.41%)409.2 V9.63 V (2.32%)9100.4 WDrop High

FAQ — 900 Amp Cable Size at 70 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 70 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 70m at 415V (voltage drop: 2.92V or 0.7%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.