⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

900 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 35 m (114.8 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.46V (0.35%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 4.81V (1.16%)
Voltage at Load413.5 VLine Loss: 2275.1 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A778.38 V (187.56%)0.0 V1283.97 V (309.39%)1213380.0 WDrop High
2.5 mm²24 A18 A467.03 V (112.54%)0.0 V770.38 V (185.63%)728028.0 WDrop High
4 mm²32 A25 A291.89 V (70.34%)123.1 V481.49 V (116.02%)455017.5 WDrop High
6 mm²41 A32 A194.6 V (46.89%)220.4 V320.99 V (77.35%)303345.0 WDrop High
10 mm²57 A44 A116.76 V (28.13%)298.2 V192.6 V (46.41%)182007.0 WDrop High
16 mm²76 A59 A72.97 V (17.58%)342.0 V120.37 V (29.01%)113754.4 WDrop High
25 mm²101 A78 A46.7 V (11.25%)368.3 V77.04 V (18.56%)72802.8 WDrop High
35 mm²125 A97 A33.36 V (8.04%)381.6 V55.03 V (13.26%)52002.0 WDrop High
50 mm²151 A118 A23.35 V (5.63%)391.6 V38.52 V (9.28%)36401.4 WDrop High
70 mm²192 A150 A16.68 V (4.02%)398.3 V27.51 V (6.63%)26001.0 WDrop High
95 mm²232 A181 A12.29 V (2.96%)402.7 V20.27 V (4.89%)19158.6 WDrop High
120 mm²269 A210 A9.73 V (2.34%)405.3 V16.05 V (3.87%)15167.3 WDrop High
150 mm²309 A241 A7.78 V (1.88%)407.2 V12.84 V (3.09%)12133.8 WDrop High
185 mm²353 A275 A6.31 V (1.52%)408.7 V10.41 V (2.51%)9838.2 WDrop High
240 mm²415 A324 A4.86 V (1.17%)410.1 V8.02 V (1.93%)7583.6 WDrop High
300 mm²477 A372 A3.89 V (0.94%)411.1 V6.42 V (1.55%)6066.9 WDrop High
400 mm²570 A445 A2.92 V (0.7%)412.1 V4.81 V (1.16%)4550.2 WDrop High

FAQ — 900 Amp Cable Size at 35 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 35 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 35m at 415V (voltage drop: 1.46V or 0.35%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.