900 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 20 m (65.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 0.83V (0.2%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.75V (0.66%)
Voltage at Load414.2 VLine Loss: 1300.0 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 20m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A444.79 V (107.18%)0.0 V733.7 V (176.79%)693360.0 WDrop High
2.5 mm²24 A18 A266.87 V (64.31%)148.1 V440.22 V (106.08%)416016.0 WDrop High
4 mm²32 A25 A166.8 V (40.19%)248.2 V275.14 V (66.3%)260010.0 WDrop High
6 mm²41 A32 A111.2 V (26.79%)303.8 V183.42 V (44.2%)173340.0 WDrop High
10 mm²57 A44 A66.72 V (16.08%)348.3 V110.05 V (26.52%)104004.0 WDrop High
16 mm²76 A59 A41.7 V (10.05%)373.3 V68.78 V (16.57%)65002.5 WDrop High
25 mm²101 A78 A26.69 V (6.43%)388.3 V44.02 V (10.61%)41601.6 WDrop High
35 mm²125 A97 A19.06 V (4.59%)395.9 V31.44 V (7.58%)29715.4 WDrop High
50 mm²151 A118 A13.34 V (3.22%)401.7 V22.01 V (5.3%)20800.8 WDrop High
70 mm²192 A150 A9.53 V (2.3%)405.5 V15.72 V (3.79%)14857.7 WDrop High
95 mm²232 A181 A7.02 V (1.69%)408.0 V11.58 V (2.79%)10947.8 WDrop High
120 mm²269 A210 A5.56 V (1.34%)409.4 V9.17 V (2.21%)8667.0 WDrop High
150 mm²309 A241 A4.45 V (1.07%)410.6 V7.34 V (1.77%)6933.6 WDrop High
185 mm²353 A275 A3.61 V (0.87%)411.4 V5.95 V (1.43%)5621.8 WDrop High
240 mm²415 A324 A2.78 V (0.67%)412.2 V4.59 V (1.1%)4333.5 WDrop High
300 mm²477 A372 A2.22 V (0.54%)412.8 V3.67 V (0.88%)3466.8 WDrop High
400 mm²570 A445 A1.67 V (0.4%)413.3 V2.75 V (0.66%)2600.1 WDrop High

FAQ — 900 Amp Cable Size at 20 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 20 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 20m at 415V (voltage drop: 0.83V or 0.2%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.