900 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 45 m (147.6 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 1.88V (0.45%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.19V (1.49%)
Voltage at Load413.1 VLine Loss: 2925.1 W
Max Power & Breaker646.92 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 45m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1000.78 V (241.15%)0.0 V1650.82 V (397.79%)1560060.0 WDrop High
2.5 mm²24 A18 A600.47 V (144.69%)0.0 V990.49 V (238.67%)936036.0 WDrop High
4 mm²32 A25 A375.29 V (90.43%)39.7 V619.06 V (149.17%)585022.5 WDrop High
6 mm²41 A32 A250.19 V (60.29%)164.8 V412.7 V (99.45%)390015.0 WDrop High
10 mm²57 A44 A150.12 V (36.17%)264.9 V247.62 V (59.67%)234009.0 WDrop High
16 mm²76 A59 A93.82 V (22.61%)321.2 V154.76 V (37.29%)146255.6 WDrop High
25 mm²101 A78 A60.05 V (14.47%)355.0 V99.05 V (23.87%)93603.6 WDrop High
35 mm²125 A97 A42.89 V (10.34%)372.1 V70.75 V (17.05%)66859.7 WDrop High
50 mm²151 A118 A30.02 V (7.23%)385.0 V49.52 V (11.93%)46801.8 WDrop High
70 mm²192 A150 A21.45 V (5.17%)393.6 V35.37 V (8.52%)33429.9 WDrop High
95 mm²232 A181 A15.8 V (3.81%)399.2 V26.07 V (6.28%)24632.5 WDrop High
120 mm²269 A210 A12.51 V (3.01%)402.5 V20.64 V (4.97%)19500.7 WDrop High
150 mm²309 A241 A10.01 V (2.41%)405.0 V16.51 V (3.98%)15600.6 WDrop High
185 mm²353 A275 A8.11 V (1.96%)406.9 V13.39 V (3.23%)12649.1 WDrop High
240 mm²415 A324 A6.25 V (1.51%)408.7 V10.32 V (2.49%)9750.4 WDrop High
300 mm²477 A372 A5.0 V (1.21%)410.0 V8.25 V (1.99%)7800.3 WDrop High
400 mm²570 A445 A3.75 V (0.9%)411.2 V6.19 V (1.49%)5850.2 WDrop High

FAQ — 900 Amp Cable Size at 45 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 900A at 45 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 45m at 415V (voltage drop: 1.88V or 0.45%).

What is the power capacity of 900A at 415V?

At unity power factor, 900A at 415V supports 646.92 kW with a standard 1000A circuit breaker.