900 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 900 A over 175 m (574.1 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 7.29V (1.06%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 24.07V (3.49%)
Voltage at Load682.7 VLine Loss: 11375.5 W
Max Power & Breaker1075.6 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 900A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3891.92 V (564.05%)0.0 V6419.85 V (930.41%)6066900.0 WDrop High
2.5 mm²24 A18 A2335.15 V (338.43%)0.0 V3851.91 V (558.25%)3640140.0 WDrop High
4 mm²32 A25 A1459.47 V (211.52%)0.0 V2407.44 V (348.9%)2275087.5 WDrop High
6 mm²41 A32 A972.98 V (141.01%)0.0 V1604.96 V (232.6%)1516725.0 WDrop High
10 mm²57 A44 A583.79 V (84.61%)106.2 V962.98 V (139.56%)910035.0 WDrop High
16 mm²76 A59 A364.87 V (52.88%)325.1 V601.86 V (87.23%)568771.9 WDrop High
25 mm²101 A78 A233.52 V (33.84%)456.5 V385.19 V (55.82%)364014.0 WDrop High
35 mm²125 A97 A166.8 V (24.17%)523.2 V275.14 V (39.87%)260010.0 WDrop High
50 mm²151 A118 A116.76 V (16.92%)573.2 V192.6 V (27.91%)182007.0 WDrop High
70 mm²192 A150 A83.4 V (12.09%)606.6 V137.57 V (19.94%)130005.0 WDrop High
95 mm²232 A181 A61.45 V (8.91%)628.5 V101.37 V (14.69%)95793.2 WDrop High
120 mm²269 A210 A48.65 V (7.05%)641.4 V80.25 V (11.63%)75836.2 WDrop High
150 mm²309 A241 A38.92 V (5.64%)651.1 V64.2 V (9.3%)60669.0 WDrop High
185 mm²353 A275 A31.56 V (4.57%)658.4 V52.05 V (7.54%)49191.1 WDrop High
240 mm²415 A324 A24.32 V (3.53%)665.7 V40.12 V (5.82%)37918.1 WDrop High
300 mm²477 A372 A19.46 V (2.82%)670.5 V32.1 V (4.65%)30334.5 WDrop High
400 mm²570 A445 A14.59 V (2.12%)675.4 V24.07 V (3.49%)22750.9 WDrop High

FAQ — 900 Amp Cable Size at 175 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 900A at 175 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 900A over 175m at 690V (voltage drop: 7.29V or 1.06%).

What is the power capacity of 900A at 690V?

At unity power factor, 900A at 690V supports 1075.6 kW with a standard 1000A circuit breaker.