Kabeltværsnit for 1000 Ampere ved 80 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 1000 A over 80 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.71V (0.93%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 12.23V (3.06%)
Voltage at Load396.3 VLine Loss: 6420.0 W
Max Power & Breaker692.82 kW1000A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 1000A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1976.85 V (494.21%)0.0 V3260.87 V (815.22%)3424000.0 WDrop High
2.5 mm²24 A18 A1186.11 V (296.53%)0.0 V1956.52 V (489.13%)2054400.0 WDrop High
4 mm²32 A25 A741.32 V (185.33%)0.0 V1222.83 V (305.71%)1284000.0 WDrop High
6 mm²41 A32 A494.21 V (123.55%)0.0 V815.22 V (203.8%)856000.0 WDrop High
10 mm²57 A44 A296.53 V (74.13%)103.5 V489.13 V (122.28%)513600.0 WDrop High
16 mm²76 A59 A185.33 V (46.33%)214.7 V305.71 V (76.43%)321000.0 WDrop High
25 mm²101 A78 A118.61 V (29.65%)281.4 V195.65 V (48.91%)205440.0 WDrop High
35 mm²125 A97 A84.72 V (21.18%)315.3 V139.75 V (34.94%)146742.9 WDrop High
50 mm²151 A118 A59.31 V (14.83%)340.7 V97.83 V (24.46%)102720.0 WDrop High
70 mm²192 A150 A42.36 V (10.59%)357.6 V69.88 V (17.47%)73371.4 WDrop High
95 mm²232 A181 A31.21 V (7.8%)368.8 V51.49 V (12.87%)54063.2 WDrop High
120 mm²269 A210 A24.71 V (6.18%)375.3 V40.76 V (10.19%)42800.0 WDrop High
150 mm²309 A241 A19.77 V (4.94%)380.2 V32.61 V (8.15%)34240.0 WDrop High
185 mm²353 A275 A16.03 V (4.01%)384.0 V26.44 V (6.61%)27762.2 WDrop High
240 mm²415 A324 A12.36 V (3.09%)387.6 V20.38 V (5.1%)21400.0 WDrop High
300 mm²477 A372 A9.88 V (2.47%)390.1 V16.3 V (4.08%)17120.0 WDrop High
400 mm²570 A445 A7.41 V (1.85%)392.6 V12.23 V (3.06%)12840.0 WDrop High

FAQ — Kabeltværsnit for 1000 Ampere ved 80 Meter (400V)

Hvilket kabeltværsnit kræves til 1000A ved 80 meter (400V)?

Til 1000 Ampere over 80 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 3.71V / 0.93%).

Hvor mange kW svarer 1000A ved 400V til?

Det svarer til 692.82 kW med en anbefalet sikring på 1000A.