Kabeltværsnit for 110 Ampere ved 100 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 100 m ved 400V.
Copper Cable (≤3% Drop)35 mm²Drop: 11.65V (2.91%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 9.61V (2.4%)
Voltage at Load388.4 VLine Loss: 2219.5 W
Max Power & Breaker76.21 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 271.82 V (67.95%) | 128.2 V | 448.37 V (112.09%) | 51788.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 163.09 V (40.77%) | 236.9 V | 269.02 V (67.26%) | 31072.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 101.93 V (25.48%) | 298.1 V | 168.14 V (42.03%) | 19420.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 67.95 V (16.99%) | 332.0 V | 112.09 V (28.02%) | 12947.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 40.77 V (10.19%) | 359.2 V | 67.26 V (16.81%) | 7768.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 25.48 V (6.37%) | 374.5 V | 42.03 V (10.51%) | 4855.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 16.31 V (4.08%) | 383.7 V | 26.9 V (6.73%) | 3107.3 W | Drop High |
| 35 mm² | 125 A | 97 A | 11.65 V (2.91%) | 388.4 V | 19.22 V (4.8%) | 2219.5 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 8.15 V (2.04%) | 391.8 V | 13.45 V (3.36%) | 1553.6 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 5.82 V (1.46%) | 394.2 V | 9.61 V (2.4%) | 1109.7 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 4.29 V (1.07%) | 395.7 V | 7.08 V (1.77%) | 817.7 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 3.4 V (0.85%) | 396.6 V | 5.6 V (1.4%) | 647.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 2.72 V (0.68%) | 397.3 V | 4.48 V (1.12%) | 517.9 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 2.2 V (0.55%) | 397.8 V | 3.64 V (0.91%) | 419.9 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 1.7 V (0.42%) | 398.3 V | 2.8 V (0.7%) | 323.7 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 1.36 V (0.34%) | 398.6 V | 2.24 V (0.56%) | 258.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.02 V (0.25%) | 399.0 V | 1.68 V (0.42%) | 194.2 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 110 Ampere ved 100 Meter (400V)
Hvilket kabeltværsnit kræves til 110A ved 100 meter (400V)?
Til 110 Ampere over 100 meter ved 400V anbefales 35 mm² kobberkabel (spændingsfald 11.65V / 2.91%).
Hvor mange kW svarer 110A ved 400V til?
Det svarer til 76.21 kW med en anbefalet sikring på 110A.
Related Lengths & Currents (400V)
110A · 5m (400V)110A · 10m (400V)110A · 15m (400V)110A · 20m (400V)110A · 25m (400V)110A · 30m (400V)110A · 35m (400V)110A · 40m (400V)110A · 45m (400V)110A · 50m (400V)110A · 60m (400V)110A · 70m (400V)10A · 100m (400V)16A · 100m (400V)20A · 100m (400V)25A · 100m (400V)32A · 100m (400V)40A · 100m (400V)50A · 100m (400V)63A · 100m (400V)80A · 100m (400V)100A · 100m (400V)125A · 100m (400V)160A · 100m (400V)200A · 100m (400V)