Kabeltværsnit for 110 Ampere ved 600 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 600 m ved 400V.
Copper Cable (≤3% Drop)240 mm²Drop: 10.19V (2.55%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 10.09V (2.52%)
Voltage at Load389.8 VLine Loss: 1942.0 W
Max Power & Breaker76.21 kW110A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1630.9 V (407.72%) | 0.0 V | 2690.22 V (672.56%) | 310728.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 978.54 V (244.63%) | 0.0 V | 1614.13 V (403.53%) | 186436.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 611.59 V (152.9%) | 0.0 V | 1008.83 V (252.21%) | 116523.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 407.72 V (101.93%) | 0.0 V | 672.56 V (168.14%) | 77682.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 244.63 V (61.16%) | 155.4 V | 403.53 V (100.88%) | 46609.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 152.9 V (38.22%) | 247.1 V | 252.21 V (63.05%) | 29130.8 W | Drop High |
| 25 mm² | 101 A | 78 A | 97.85 V (24.46%) | 302.1 V | 161.41 V (40.35%) | 18643.7 W | Drop High |
| 35 mm² | 125 A | 97 A | 69.9 V (17.47%) | 330.1 V | 115.3 V (28.82%) | 13316.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 48.93 V (12.23%) | 351.1 V | 80.71 V (20.18%) | 9321.8 W | Drop High |
| 70 mm² | 192 A | 150 A | 34.95 V (8.74%) | 365.1 V | 57.65 V (14.41%) | 6658.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 25.75 V (6.44%) | 374.2 V | 42.48 V (10.62%) | 4906.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 20.39 V (5.1%) | 379.6 V | 33.63 V (8.41%) | 3884.1 W | Drop High |
| 150 mm² | 309 A | 241 A | 16.31 V (4.08%) | 383.7 V | 26.9 V (6.73%) | 3107.3 W | ~ ≤5% |
| 185 mm² | 353 A | 275 A | 13.22 V (3.31%) | 386.8 V | 21.81 V (5.45%) | 2519.4 W | ~ ≤5% |
| 240 mm² | 415 A | 324 A | 10.19 V (2.55%) | 389.8 V | 16.81 V (4.2%) | 1942.0 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 8.15 V (2.04%) | 391.8 V | 13.45 V (3.36%) | 1553.6 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 6.12 V (1.53%) | 393.9 V | 10.09 V (2.52%) | 1165.2 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 110 Ampere ved 600 Meter (400V)
Hvilket kabeltværsnit kræves til 110A ved 600 meter (400V)?
Til 110 Ampere over 600 meter ved 400V anbefales 240 mm² kobberkabel (spændingsfald 10.19V / 2.55%).
Hvor mange kW svarer 110A ved 400V til?
Det svarer til 76.21 kW med en anbefalet sikring på 110A.
Related Lengths & Currents (400V)
110A · 5m (400V)110A · 10m (400V)110A · 15m (400V)110A · 20m (400V)110A · 25m (400V)110A · 30m (400V)110A · 35m (400V)110A · 40m (400V)110A · 45m (400V)110A · 50m (400V)110A · 60m (400V)110A · 70m (400V)10A · 600m (400V)16A · 600m (400V)20A · 600m (400V)25A · 600m (400V)32A · 600m (400V)40A · 600m (400V)50A · 600m (400V)63A · 600m (400V)80A · 600m (400V)100A · 600m (400V)125A · 600m (400V)160A · 600m (400V)200A · 600m (400V)