Kabeltværsnit for 15 Ampere ved 25 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 15 A over 25 m ved 400V.
Copper Cable (≤3% Drop)1.5 mm²Drop: 9.27V (2.32%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 9.17V (2.29%)
Voltage at Load390.7 VLine Loss: 240.7 W
Max Power & Breaker10.39 kW15A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 25m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 9.27 V (2.32%) | 390.7 V | 15.29 V (3.82%) | 240.7 W | ✓ OK (≤3%) |
| 2.5 mm² | 24 A | 18 A | 5.56 V (1.39%) | 394.4 V | 9.17 V (2.29%) | 144.4 W | ✓ OK (≤3%) |
| 4 mm² | 32 A | 25 A | 3.47 V (0.87%) | 396.5 V | 5.73 V (1.43%) | 90.3 W | ✓ OK (≤3%) |
| 6 mm² | 41 A | 32 A | 2.32 V (0.58%) | 397.7 V | 3.82 V (0.96%) | 60.2 W | ✓ OK (≤3%) |
| 10 mm² | 57 A | 44 A | 1.39 V (0.35%) | 398.6 V | 2.29 V (0.57%) | 36.1 W | ✓ OK (≤3%) |
| 16 mm² | 76 A | 59 A | 0.87 V (0.22%) | 399.1 V | 1.43 V (0.36%) | 22.6 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 0.56 V (0.14%) | 399.4 V | 0.92 V (0.23%) | 14.4 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 0.4 V (0.1%) | 399.6 V | 0.66 V (0.16%) | 10.3 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 7.2 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 0.2 V (0.05%) | 399.8 V | 0.33 V (0.08%) | 5.2 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 0.15 V (0.04%) | 399.9 V | 0.24 V (0.06%) | 3.8 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.12 V (0.03%) | 399.9 V | 0.19 V (0.05%) | 3.0 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.09 V (0.02%) | 399.9 V | 0.15 V (0.04%) | 2.4 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.08 V (0.02%) | 399.9 V | 0.12 V (0.03%) | 2.0 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.06 V (0.01%) | 399.9 V | 0.1 V (0.02%) | 1.5 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.05 V (0.01%) | 400.0 V | 0.08 V (0.02%) | 1.2 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.03 V (0.01%) | 400.0 V | 0.06 V (0.01%) | 0.9 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 15 Ampere ved 25 Meter (400V)
Hvilket kabeltværsnit kræves til 15A ved 25 meter (400V)?
Til 15 Ampere over 25 meter ved 400V anbefales 1.5 mm² kobberkabel (spændingsfald 9.27V / 2.32%).
Hvor mange kW svarer 15A ved 400V til?
Det svarer til 10.39 kW med en anbefalet sikring på 15A.
Related Lengths & Currents (400V)
15A · 5m (400V)15A · 10m (400V)15A · 15m (400V)15A · 20m (400V)15A · 30m (400V)15A · 35m (400V)15A · 40m (400V)15A · 45m (400V)15A · 50m (400V)15A · 60m (400V)15A · 70m (400V)10A · 25m (400V)16A · 25m (400V)20A · 25m (400V)25A · 25m (400V)32A · 25m (400V)40A · 25m (400V)50A · 25m (400V)63A · 25m (400V)80A · 25m (400V)100A · 25m (400V)125A · 25m (400V)160A · 25m (400V)200A · 25m (400V)