Kabeltværsnit for 175 Ampere ved 150 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 150 m ved 400V.
Copper Cable (≤3% Drop)95 mm²Drop: 10.24V (2.56%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 10.7V (2.67%)
Voltage at Load389.8 VLine Loss: 3104.4 W
Max Power & Breaker121.24 kW175A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 150m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 648.65 V (162.16%) | 0.0 V | 1069.97 V (267.49%) | 196612.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 389.19 V (97.3%) | 10.8 V | 641.98 V (160.5%) | 117967.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 243.24 V (60.81%) | 156.8 V | 401.24 V (100.31%) | 73729.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 162.16 V (40.54%) | 237.8 V | 267.49 V (66.87%) | 49153.1 W | Drop High |
| 10 mm² | 57 A | 44 A | 97.3 V (24.32%) | 302.7 V | 160.5 V (40.12%) | 29491.9 W | Drop High |
| 16 mm² | 76 A | 59 A | 60.81 V (15.2%) | 339.2 V | 100.31 V (25.08%) | 18432.4 W | Drop High |
| 25 mm² | 101 A | 78 A | 38.92 V (9.73%) | 361.1 V | 64.2 V (16.05%) | 11796.7 W | Drop High |
| 35 mm² | 125 A | 97 A | 27.8 V (6.95%) | 372.2 V | 45.86 V (11.46%) | 8426.2 W | Drop High |
| 50 mm² | 151 A | 118 A | 19.46 V (4.86%) | 380.5 V | 32.1 V (8.02%) | 5898.4 W | Drop High |
| 70 mm² | 192 A | 150 A | 13.9 V (3.47%) | 386.1 V | 22.93 V (5.73%) | 4213.1 W | ~ ≤5% |
| 95 mm² | 232 A | 181 A | 10.24 V (2.56%) | 389.8 V | 16.89 V (4.22%) | 3104.4 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 8.11 V (2.03%) | 391.9 V | 13.37 V (3.34%) | 2457.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 6.49 V (1.62%) | 393.5 V | 10.7 V (2.67%) | 1966.1 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 5.26 V (1.31%) | 394.7 V | 8.68 V (2.17%) | 1594.2 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 4.05 V (1.01%) | 395.9 V | 6.69 V (1.67%) | 1228.8 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 3.24 V (0.81%) | 396.8 V | 5.35 V (1.34%) | 983.1 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 2.43 V (0.61%) | 397.6 V | 4.01 V (1.0%) | 737.3 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 175 Ampere ved 150 Meter (400V)
Hvilket kabeltværsnit kræves til 175A ved 150 meter (400V)?
Til 175 Ampere over 150 meter ved 400V anbefales 95 mm² kobberkabel (spændingsfald 10.24V / 2.56%).
Hvor mange kW svarer 175A ved 400V til?
Det svarer til 121.24 kW med en anbefalet sikring på 175A.
Related Lengths & Currents (400V)
175A · 5m (400V)175A · 10m (400V)175A · 15m (400V)175A · 20m (400V)175A · 25m (400V)175A · 30m (400V)175A · 35m (400V)175A · 40m (400V)175A · 45m (400V)175A · 50m (400V)175A · 60m (400V)175A · 70m (400V)10A · 150m (400V)16A · 150m (400V)20A · 150m (400V)25A · 150m (400V)32A · 150m (400V)40A · 150m (400V)50A · 150m (400V)63A · 150m (400V)80A · 150m (400V)100A · 150m (400V)125A · 150m (400V)160A · 150m (400V)200A · 150m (400V)