Kabeltværsnit for 175 Ampere ved 600 Meter (400V)
Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 175 A over 600 m ved 400V.
Copper Cable (≤3% Drop)400 mm²Drop: 9.73V (2.43%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 16.05V (4.01%)
Voltage at Load390.3 VLine Loss: 2949.2 W
Max Power & Breaker121.24 kW175A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 175A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 2594.61 V (648.65%) | 0.0 V | 4279.9 V (1069.97%) | 786450.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 1556.77 V (389.19%) | 0.0 V | 2567.94 V (641.98%) | 471870.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 972.98 V (243.24%) | 0.0 V | 1604.96 V (401.24%) | 294918.8 W | Drop High |
| 6 mm² | 41 A | 32 A | 648.65 V (162.16%) | 0.0 V | 1069.97 V (267.49%) | 196612.5 W | Drop High |
| 10 mm² | 57 A | 44 A | 389.19 V (97.3%) | 10.8 V | 641.98 V (160.5%) | 117967.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 243.24 V (60.81%) | 156.8 V | 401.24 V (100.31%) | 73729.7 W | Drop High |
| 25 mm² | 101 A | 78 A | 155.68 V (38.92%) | 244.3 V | 256.79 V (64.2%) | 47187.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 111.2 V (27.8%) | 288.8 V | 183.42 V (45.86%) | 33705.0 W | Drop High |
| 50 mm² | 151 A | 118 A | 77.84 V (19.46%) | 322.2 V | 128.4 V (32.1%) | 23593.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 55.6 V (13.9%) | 344.4 V | 91.71 V (22.93%) | 16852.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 40.97 V (10.24%) | 359.0 V | 67.58 V (16.89%) | 12417.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 32.43 V (8.11%) | 367.6 V | 53.5 V (13.37%) | 9830.6 W | Drop High |
| 150 mm² | 309 A | 241 A | 25.95 V (6.49%) | 374.1 V | 42.8 V (10.7%) | 7864.5 W | Drop High |
| 185 mm² | 353 A | 275 A | 21.04 V (5.26%) | 379.0 V | 34.7 V (8.68%) | 6376.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 16.22 V (4.05%) | 383.8 V | 26.75 V (6.69%) | 4915.3 W | ~ ≤5% |
| 300 mm² | 477 A | 372 A | 12.97 V (3.24%) | 387.0 V | 21.4 V (5.35%) | 3932.2 W | ~ ≤5% |
| 400 mm² | 570 A | 445 A | 9.73 V (2.43%) | 390.3 V | 16.05 V (4.01%) | 2949.2 W | ✓ OK (≤3%) |
FAQ — Kabeltværsnit for 175 Ampere ved 600 Meter (400V)
Hvilket kabeltværsnit kræves til 175A ved 600 meter (400V)?
Til 175 Ampere over 600 meter ved 400V anbefales 400 mm² kobberkabel (spændingsfald 9.73V / 2.43%).
Hvor mange kW svarer 175A ved 400V til?
Det svarer til 121.24 kW med en anbefalet sikring på 175A.
Related Lengths & Currents (400V)
175A · 5m (400V)175A · 10m (400V)175A · 15m (400V)175A · 20m (400V)175A · 25m (400V)175A · 30m (400V)175A · 35m (400V)175A · 40m (400V)175A · 45m (400V)175A · 50m (400V)175A · 60m (400V)175A · 70m (400V)10A · 600m (400V)16A · 600m (400V)20A · 600m (400V)25A · 600m (400V)32A · 600m (400V)40A · 600m (400V)50A · 600m (400V)63A · 600m (400V)80A · 600m (400V)100A · 600m (400V)125A · 600m (400V)160A · 600m (400V)200A · 600m (400V)