Kabeltværsnit for 425 Ampere ved 80 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 425 A over 80 m ved 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 4.2V (1.05%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.2V (1.3%)
Voltage at Load395.8 VLine Loss: 3092.3 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A840.16 V (210.04%)0.0 V1385.87 V (346.47%)618460.0 WDrop High
2.5 mm²24 A18 A504.1 V (126.02%)0.0 V831.52 V (207.88%)371076.0 WDrop High
4 mm²32 A25 A315.06 V (78.77%)84.9 V519.7 V (129.93%)231922.5 WDrop High
6 mm²41 A32 A210.04 V (52.51%)190.0 V346.47 V (86.62%)154615.0 WDrop High
10 mm²57 A44 A126.02 V (31.51%)274.0 V207.88 V (51.97%)92769.0 WDrop High
16 mm²76 A59 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
25 mm²101 A78 A50.41 V (12.6%)349.6 V83.15 V (20.79%)37107.6 WDrop High
35 mm²125 A97 A36.01 V (9.0%)364.0 V59.39 V (14.85%)26505.4 WDrop High
50 mm²151 A118 A25.2 V (6.3%)374.8 V41.58 V (10.39%)18553.8 WDrop High
70 mm²192 A150 A18.0 V (4.5%)382.0 V29.7 V (7.42%)13252.7 WDrop High
95 mm²232 A181 A13.27 V (3.32%)386.7 V21.88 V (5.47%)9765.2 WDrop High
120 mm²269 A210 A10.5 V (2.63%)389.5 V17.32 V (4.33%)7730.8 WDrop High
150 mm²309 A241 A8.4 V (2.1%)391.6 V13.86 V (3.46%)6184.6 WDrop High
185 mm²353 A275 A6.81 V (1.7%)393.2 V11.24 V (2.81%)5014.5 WDrop High
240 mm²415 A324 A5.25 V (1.31%)394.7 V8.66 V (2.17%)3865.4 WDrop High
300 mm²477 A372 A4.2 V (1.05%)395.8 V6.93 V (1.73%)3092.3 W✓ OK (≤3%)
400 mm²570 A445 A3.15 V (0.79%)396.8 V5.2 V (1.3%)2319.2 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 425 Ampere ved 80 Meter (400V)

Hvilket kabeltværsnit kræves til 425A ved 80 meter (400V)?

Til 425 Ampere over 80 meter ved 400V anbefales 300 mm² kobberkabel (spændingsfald 4.2V / 1.05%).

Hvor mange kW svarer 425A ved 400V til?

Det svarer til 294.45 kW med en anbefalet sikring på 450A.