Kabeltværsnit for 60 Ampere ved 600 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 60 A over 600 m ved 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 6.42V (2.79%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.35V (2.76%)
Voltage at Load223.6 VLine Loss: 385.2 W
Max Power & Breaker13.8 kW60A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 60A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1027.2 V (446.61%)0.0 V1694.4 V (736.7%)61632.0 WDrop High
2.5 mm²24 A18 A616.32 V (267.97%)0.0 V1016.64 V (442.02%)36979.2 WDrop High
4 mm²32 A25 A385.2 V (167.48%)0.0 V635.4 V (276.26%)23112.0 WDrop High
6 mm²41 A32 A256.8 V (111.65%)0.0 V423.6 V (184.17%)15408.0 WDrop High
10 mm²57 A44 A154.08 V (66.99%)75.9 V254.16 V (110.5%)9244.8 WDrop High
16 mm²76 A59 A96.3 V (41.87%)133.7 V158.85 V (69.07%)5778.0 WDrop High
25 mm²101 A78 A61.63 V (26.8%)168.4 V101.66 V (44.2%)3697.9 WDrop High
35 mm²125 A97 A44.02 V (19.14%)186.0 V72.62 V (31.57%)2641.4 WDrop High
50 mm²151 A118 A30.82 V (13.4%)199.2 V50.83 V (22.1%)1849.0 WDrop High
70 mm²192 A150 A22.01 V (9.57%)208.0 V36.31 V (15.79%)1320.7 WDrop High
95 mm²232 A181 A16.22 V (7.05%)213.8 V26.75 V (11.63%)973.1 WDrop High
120 mm²269 A210 A12.84 V (5.58%)217.2 V21.18 V (9.21%)770.4 WDrop High
150 mm²309 A241 A10.27 V (4.47%)219.7 V16.94 V (7.37%)616.3 W~ ≤5%
185 mm²353 A275 A8.33 V (3.62%)221.7 V13.74 V (5.97%)499.7 W~ ≤5%
240 mm²415 A324 A6.42 V (2.79%)223.6 V10.59 V (4.6%)385.2 W✓ OK (≤3%)
300 mm²477 A372 A5.14 V (2.23%)224.9 V8.47 V (3.68%)308.2 W✓ OK (≤3%)
400 mm²570 A445 A3.85 V (1.67%)226.1 V6.35 V (2.76%)231.1 W✓ OK (≤3%)

FAQ — Kabeltværsnit for 60 Ampere ved 600 Meter (230V)

Hvilket kabeltværsnit kræves til 60A ved 600 meter (230V)?

Til 60 Ampere over 600 meter ved 230V anbefales 240 mm² kobberkabel (spændingsfald 6.42V / 2.79%).

Hvor mange kW svarer 60A ved 230V til?

Det svarer til 13.8 kW med en anbefalet sikring på 60A.