Kabeltværsnit for 600 Ampere ved 80 Meter (400V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 600 A over 80 m ved 400V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 2.23V (0.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.34V (1.83%)
Voltage at Load397.8 VLine Loss: 2311.2 W
Max Power & Breaker415.69 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 600A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1186.11 V (296.53%)0.0 V1956.52 V (489.13%)1232640.0 WDrop High
2.5 mm²24 A18 A711.67 V (177.92%)0.0 V1173.91 V (293.48%)739584.0 WDrop High
4 mm²32 A25 A444.79 V (111.2%)0.0 V733.7 V (183.42%)462240.0 WDrop High
6 mm²41 A32 A296.53 V (74.13%)103.5 V489.13 V (122.28%)308160.0 WDrop High
10 mm²57 A44 A177.92 V (44.48%)222.1 V293.48 V (73.37%)184896.0 WDrop High
16 mm²76 A59 A111.2 V (27.8%)288.8 V183.42 V (45.86%)115560.0 WDrop High
25 mm²101 A78 A71.17 V (17.79%)328.8 V117.39 V (29.35%)73958.4 WDrop High
35 mm²125 A97 A50.83 V (12.71%)349.2 V83.85 V (20.96%)52827.4 WDrop High
50 mm²151 A118 A35.58 V (8.9%)364.4 V58.7 V (14.67%)36979.2 WDrop High
70 mm²192 A150 A25.42 V (6.35%)374.6 V41.93 V (10.48%)26413.7 WDrop High
95 mm²232 A181 A18.73 V (4.68%)381.3 V30.89 V (7.72%)19462.7 WDrop High
120 mm²269 A210 A14.83 V (3.71%)385.2 V24.46 V (6.11%)15408.0 WDrop High
150 mm²309 A241 A11.86 V (2.97%)388.1 V19.57 V (4.89%)12326.4 WDrop High
185 mm²353 A275 A9.62 V (2.4%)390.4 V15.86 V (3.97%)9994.4 WDrop High
240 mm²415 A324 A7.41 V (1.85%)392.6 V12.23 V (3.06%)7704.0 WDrop High
300 mm²477 A372 A5.93 V (1.48%)394.1 V9.78 V (2.45%)6163.2 WDrop High
400 mm²570 A445 A4.45 V (1.11%)395.6 V7.34 V (1.83%)4622.4 WDrop High

FAQ — Kabeltværsnit for 600 Ampere ved 80 Meter (400V)

Hvilket kabeltværsnit kræves til 600A ved 80 meter (400V)?

Til 600 Ampere over 80 meter ved 400V anbefales 2× 400 mm² kobberkabel (spændingsfald 2.23V / 0.56%).

Hvor mange kW svarer 600A ved 400V til?

Det svarer til 415.69 kW med en anbefalet sikring på 600A.