Kabelarea för 100 Ampere vid 5 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 100 A över 5 m vid 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 0.86V (0.37%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 0.71V (0.31%)
Voltage at Load229.1 VLine Loss: 85.6 W
Max Power & Breaker23.0 kW100A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 100A at 5m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A14.27 V (6.2%)215.7 V23.53 V (10.23%)1426.7 WDrop High
2.5 mm²24 A18 A8.56 V (3.72%)221.4 V14.12 V (6.14%)856.0 WDrop High
4 mm²32 A25 A5.35 V (2.33%)224.7 V8.82 V (3.84%)535.0 WDrop High
6 mm²41 A32 A3.57 V (1.55%)226.4 V5.88 V (2.56%)356.7 WDrop High
10 mm²57 A44 A2.14 V (0.93%)227.9 V3.53 V (1.53%)214.0 WDrop High
16 mm²76 A59 A1.34 V (0.58%)228.7 V2.21 V (0.96%)133.8 WDrop High
25 mm²101 A78 A0.86 V (0.37%)229.1 V1.41 V (0.61%)85.6 W✓ OK (≤3%)
35 mm²125 A97 A0.61 V (0.27%)229.4 V1.01 V (0.44%)61.1 W✓ OK (≤3%)
50 mm²151 A118 A0.43 V (0.19%)229.6 V0.71 V (0.31%)42.8 W✓ OK (≤3%)
70 mm²192 A150 A0.31 V (0.13%)229.7 V0.5 V (0.22%)30.6 W✓ OK (≤3%)
95 mm²232 A181 A0.23 V (0.1%)229.8 V0.37 V (0.16%)22.5 W✓ OK (≤3%)
120 mm²269 A210 A0.18 V (0.08%)229.8 V0.29 V (0.13%)17.8 W✓ OK (≤3%)
150 mm²309 A241 A0.14 V (0.06%)229.9 V0.24 V (0.1%)14.3 W✓ OK (≤3%)
185 mm²353 A275 A0.12 V (0.05%)229.9 V0.19 V (0.08%)11.6 W✓ OK (≤3%)
240 mm²415 A324 A0.09 V (0.04%)229.9 V0.15 V (0.06%)8.9 W✓ OK (≤3%)
300 mm²477 A372 A0.07 V (0.03%)229.9 V0.12 V (0.05%)7.1 W✓ OK (≤3%)
400 mm²570 A445 A0.05 V (0.02%)229.9 V0.09 V (0.04%)5.3 W✓ OK (≤3%)

FAQ — Kabelarea för 100 Ampere vid 5 Meter (230V)

Vilken kabelarea krävs för 100A vid 5 meter (230V)?

För 100 Ampere över 5 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (0.86V / 0.37%).

Hur stor effekt motsvarar 100A vid 230V?

Det motsvarar 23.0 kW med en rekommenderad säkring på 100A.