Kabelarea för 110 Ampere vid 400 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 400 m vid 400V.

Copper Cable (≤3% Drop)150 mm²Drop: 10.87V (2.72%)
Aluminum Cable (≤3% Drop)240 mm²Drop: 11.21V (2.8%)
Voltage at Load389.1 VLine Loss: 2071.5 W
Max Power & Breaker76.21 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1087.27 V (271.82%)0.0 V1793.48 V (448.37%)207152.0 WDrop High
2.5 mm²24 A18 A652.36 V (163.09%)0.0 V1076.09 V (269.02%)124291.2 WDrop High
4 mm²32 A25 A407.72 V (101.93%)0.0 V672.56 V (168.14%)77682.0 WDrop High
6 mm²41 A32 A271.82 V (67.95%)128.2 V448.37 V (112.09%)51788.0 WDrop High
10 mm²57 A44 A163.09 V (40.77%)236.9 V269.02 V (67.26%)31072.8 WDrop High
16 mm²76 A59 A101.93 V (25.48%)298.1 V168.14 V (42.03%)19420.5 WDrop High
25 mm²101 A78 A65.24 V (16.31%)334.8 V107.61 V (26.9%)12429.1 WDrop High
35 mm²125 A97 A46.6 V (11.65%)353.4 V76.86 V (19.22%)8877.9 WDrop High
50 mm²151 A118 A32.62 V (8.15%)367.4 V53.8 V (13.45%)6214.6 WDrop High
70 mm²192 A150 A23.3 V (5.82%)376.7 V38.43 V (9.61%)4439.0 WDrop High
95 mm²232 A181 A17.17 V (4.29%)382.8 V28.32 V (7.08%)3270.8 W~ ≤5%
120 mm²269 A210 A13.59 V (3.4%)386.4 V22.42 V (5.6%)2589.4 W~ ≤5%
150 mm²309 A241 A10.87 V (2.72%)389.1 V17.93 V (4.48%)2071.5 W✓ OK (≤3%)
185 mm²353 A275 A8.82 V (2.2%)391.2 V14.54 V (3.64%)1679.6 W✓ OK (≤3%)
240 mm²415 A324 A6.8 V (1.7%)393.2 V11.21 V (2.8%)1294.7 W✓ OK (≤3%)
300 mm²477 A372 A5.44 V (1.36%)394.6 V8.97 V (2.24%)1035.8 W✓ OK (≤3%)
400 mm²570 A445 A4.08 V (1.02%)395.9 V6.73 V (1.68%)776.8 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 400 Meter (400V)

Vilken kabelarea krävs för 110A vid 400 meter (400V)?

För 110 Ampere över 400 meter vid 400V rekommenderas 150 mm² kopparkabel för att hålla spänningsfallet under 3% (10.87V / 2.72%).

Hur stor effekt motsvarar 110A vid 400V?

Det motsvarar 76.21 kW med en rekommenderad säkring på 110A.