Kabelarea för 125 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 10 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 1.32V (0.33%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 1.09V (0.27%)
Voltage at Load398.7 VLine Loss: 286.6 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A30.89 V (7.72%)369.1 V50.95 V (12.74%)6687.5 WDrop High
2.5 mm²24 A18 A18.53 V (4.63%)381.5 V30.57 V (7.64%)4012.5 WDrop High
4 mm²32 A25 A11.58 V (2.9%)388.4 V19.11 V (4.78%)2507.8 WDrop High
6 mm²41 A32 A7.72 V (1.93%)392.3 V12.74 V (3.18%)1671.9 WDrop High
10 mm²57 A44 A4.63 V (1.16%)395.4 V7.64 V (1.91%)1003.1 WDrop High
16 mm²76 A59 A2.9 V (0.72%)397.1 V4.78 V (1.19%)627.0 WDrop High
25 mm²101 A78 A1.85 V (0.46%)398.1 V3.06 V (0.76%)401.2 WDrop High
35 mm²125 A97 A1.32 V (0.33%)398.7 V2.18 V (0.55%)286.6 W✓ OK (≤3%)
50 mm²151 A118 A0.93 V (0.23%)399.1 V1.53 V (0.38%)200.6 W✓ OK (≤3%)
70 mm²192 A150 A0.66 V (0.17%)399.3 V1.09 V (0.27%)143.3 W✓ OK (≤3%)
95 mm²232 A181 A0.49 V (0.12%)399.5 V0.8 V (0.2%)105.6 W✓ OK (≤3%)
120 mm²269 A210 A0.39 V (0.1%)399.6 V0.64 V (0.16%)83.6 W✓ OK (≤3%)
150 mm²309 A241 A0.31 V (0.08%)399.7 V0.51 V (0.13%)66.9 W✓ OK (≤3%)
185 mm²353 A275 A0.25 V (0.06%)399.7 V0.41 V (0.1%)54.2 W✓ OK (≤3%)
240 mm²415 A324 A0.19 V (0.05%)399.8 V0.32 V (0.08%)41.8 W✓ OK (≤3%)
300 mm²477 A372 A0.15 V (0.04%)399.8 V0.25 V (0.06%)33.4 W✓ OK (≤3%)
400 mm²570 A445 A0.12 V (0.03%)399.9 V0.19 V (0.05%)25.1 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 125A vid 10 meter (400V)?

För 125 Ampere över 10 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (1.32V / 0.33%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.