Kabelarea för 125 Ampere vid 60 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 125 A över 60 m vid 400V.

Copper Cable (≤3% Drop)35 mm²Drop: 7.94V (1.99%)
Aluminum Cable (≤3% Drop)70 mm²Drop: 6.55V (1.64%)
Voltage at Load392.1 VLine Loss: 1719.6 W
Max Power & Breaker86.6 kW125A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 125A at 60m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A185.33 V (46.33%)214.7 V305.71 V (76.43%)40125.0 WDrop High
2.5 mm²24 A18 A111.2 V (27.8%)288.8 V183.42 V (45.86%)24075.0 WDrop High
4 mm²32 A25 A69.5 V (17.37%)330.5 V114.64 V (28.66%)15046.9 WDrop High
6 mm²41 A32 A46.33 V (11.58%)353.7 V76.43 V (19.11%)10031.2 WDrop High
10 mm²57 A44 A27.8 V (6.95%)372.2 V45.86 V (11.46%)6018.8 WDrop High
16 mm²76 A59 A17.37 V (4.34%)382.6 V28.66 V (7.17%)3761.7 WDrop High
25 mm²101 A78 A11.12 V (2.78%)388.9 V18.34 V (4.59%)2407.5 WDrop High
35 mm²125 A97 A7.94 V (1.99%)392.1 V13.1 V (3.28%)1719.6 W✓ OK (≤3%)
50 mm²151 A118 A5.56 V (1.39%)394.4 V9.17 V (2.29%)1203.8 W✓ OK (≤3%)
70 mm²192 A150 A3.97 V (0.99%)396.0 V6.55 V (1.64%)859.8 W✓ OK (≤3%)
95 mm²232 A181 A2.93 V (0.73%)397.1 V4.83 V (1.21%)633.6 W✓ OK (≤3%)
120 mm²269 A210 A2.32 V (0.58%)397.7 V3.82 V (0.96%)501.6 W✓ OK (≤3%)
150 mm²309 A241 A1.85 V (0.46%)398.1 V3.06 V (0.76%)401.2 W✓ OK (≤3%)
185 mm²353 A275 A1.5 V (0.38%)398.5 V2.48 V (0.62%)325.3 W✓ OK (≤3%)
240 mm²415 A324 A1.16 V (0.29%)398.8 V1.91 V (0.48%)250.8 W✓ OK (≤3%)
300 mm²477 A372 A0.93 V (0.23%)399.1 V1.53 V (0.38%)200.6 W✓ OK (≤3%)
400 mm²570 A445 A0.69 V (0.17%)399.3 V1.15 V (0.29%)150.5 W✓ OK (≤3%)

FAQ — Kabelarea för 125 Ampere vid 60 Meter (400V)

Vilken kabelarea krävs för 125A vid 60 meter (400V)?

För 125 Ampere över 60 meter vid 400V rekommenderas 35 mm² kopparkabel för att hålla spänningsfallet under 3% (7.94V / 1.99%).

Hur stor effekt motsvarar 125A vid 400V?

Det motsvarar 86.6 kW med en rekommenderad säkring på 125A.