Kabelarea för 15 Ampere vid 175 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 15 A över 175 m vid 230V.

Copper Cable (≤3% Drop)25 mm²Drop: 4.49V (1.95%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 5.29V (2.3%)
Voltage at Load225.5 VLine Loss: 67.4 W
Max Power & Breaker3.45 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A74.9 V (32.57%)155.1 V123.55 V (53.72%)1123.5 WDrop High
2.5 mm²24 A18 A44.94 V (19.54%)185.1 V74.13 V (32.23%)674.1 WDrop High
4 mm²32 A25 A28.09 V (12.21%)201.9 V46.33 V (20.14%)421.3 WDrop High
6 mm²41 A32 A18.72 V (8.14%)211.3 V30.89 V (13.43%)280.9 WDrop High
10 mm²57 A44 A11.23 V (4.88%)218.8 V18.53 V (8.06%)168.5 W~ ≤5%
16 mm²76 A59 A7.02 V (3.05%)223.0 V11.58 V (5.04%)105.3 W~ ≤5%
25 mm²101 A78 A4.49 V (1.95%)225.5 V7.41 V (3.22%)67.4 W✓ OK (≤3%)
35 mm²125 A97 A3.21 V (1.4%)226.8 V5.29 V (2.3%)48.1 W✓ OK (≤3%)
50 mm²151 A118 A2.25 V (0.98%)227.8 V3.71 V (1.61%)33.7 W✓ OK (≤3%)
70 mm²192 A150 A1.6 V (0.7%)228.4 V2.65 V (1.15%)24.1 W✓ OK (≤3%)
95 mm²232 A181 A1.18 V (0.51%)228.8 V1.95 V (0.85%)17.7 W✓ OK (≤3%)
120 mm²269 A210 A0.94 V (0.41%)229.1 V1.54 V (0.67%)14.0 W✓ OK (≤3%)
150 mm²309 A241 A0.75 V (0.33%)229.3 V1.24 V (0.54%)11.2 W✓ OK (≤3%)
185 mm²353 A275 A0.61 V (0.26%)229.4 V1.0 V (0.44%)9.1 W✓ OK (≤3%)
240 mm²415 A324 A0.47 V (0.2%)229.5 V0.77 V (0.34%)7.0 W✓ OK (≤3%)
300 mm²477 A372 A0.37 V (0.16%)229.6 V0.62 V (0.27%)5.6 W✓ OK (≤3%)
400 mm²570 A445 A0.28 V (0.12%)229.7 V0.46 V (0.2%)4.2 W✓ OK (≤3%)

FAQ — Kabelarea för 15 Ampere vid 175 Meter (230V)

Vilken kabelarea krävs för 15A vid 175 meter (230V)?

För 15 Ampere över 175 meter vid 230V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (4.49V / 1.95%).

Hur stor effekt motsvarar 15A vid 230V?

Det motsvarar 3.45 kW med en rekommenderad säkring på 15A.