Kabelarea för 150 Ampere vid 200 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 150 A över 200 m vid 230V.

Copper Cable (≤3% Drop)240 mm²Drop: 5.35V (2.33%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 5.29V (2.3%)
Voltage at Load224.7 VLine Loss: 802.5 W
Max Power & Breaker34.5 kW150A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 150A at 200m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A856.0 V (372.17%)0.0 V1412.0 V (613.91%)128400.0 WDrop High
2.5 mm²24 A18 A513.6 V (223.3%)0.0 V847.2 V (368.35%)77040.0 WDrop High
4 mm²32 A25 A321.0 V (139.57%)0.0 V529.5 V (230.22%)48150.0 WDrop High
6 mm²41 A32 A214.0 V (93.04%)16.0 V353.0 V (153.48%)32100.0 WDrop High
10 mm²57 A44 A128.4 V (55.83%)101.6 V211.8 V (92.09%)19260.0 WDrop High
16 mm²76 A59 A80.25 V (34.89%)149.8 V132.38 V (57.55%)12037.5 WDrop High
25 mm²101 A78 A51.36 V (22.33%)178.6 V84.72 V (36.83%)7704.0 WDrop High
35 mm²125 A97 A36.69 V (15.95%)193.3 V60.51 V (26.31%)5502.9 WDrop High
50 mm²151 A118 A25.68 V (11.17%)204.3 V42.36 V (18.42%)3852.0 WDrop High
70 mm²192 A150 A18.34 V (7.98%)211.7 V30.26 V (13.16%)2751.4 WDrop High
95 mm²232 A181 A13.52 V (5.88%)216.5 V22.29 V (9.69%)2027.4 WDrop High
120 mm²269 A210 A10.7 V (4.65%)219.3 V17.65 V (7.67%)1605.0 W~ ≤5%
150 mm²309 A241 A8.56 V (3.72%)221.4 V14.12 V (6.14%)1284.0 W~ ≤5%
185 mm²353 A275 A6.94 V (3.02%)223.1 V11.45 V (4.98%)1041.1 W~ ≤5%
240 mm²415 A324 A5.35 V (2.33%)224.7 V8.82 V (3.84%)802.5 W✓ OK (≤3%)
300 mm²477 A372 A4.28 V (1.86%)225.7 V7.06 V (3.07%)642.0 W✓ OK (≤3%)
400 mm²570 A445 A3.21 V (1.4%)226.8 V5.29 V (2.3%)481.5 W✓ OK (≤3%)

FAQ — Kabelarea för 150 Ampere vid 200 Meter (230V)

Vilken kabelarea krävs för 150A vid 200 meter (230V)?

För 150 Ampere över 200 meter vid 230V rekommenderas 240 mm² kopparkabel för att hålla spänningsfallet under 3% (5.35V / 2.33%).

Hur stor effekt motsvarar 150A vid 230V?

Det motsvarar 34.5 kW med en rekommenderad säkring på 150A.