Kabelarea för 16 Ampere vid 10 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 10 m vid 400V.

Copper Cable (≤3% Drop)1.5 mm²Drop: 3.95V (0.99%)
Aluminum Cable (≤3% Drop)2.5 mm²Drop: 3.91V (0.98%)
Voltage at Load396.0 VLine Loss: 109.6 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 10m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3.95 V (0.99%)396.0 V6.52 V (1.63%)109.6 W✓ OK (≤3%)
2.5 mm²24 A18 A2.37 V (0.59%)397.6 V3.91 V (0.98%)65.7 W✓ OK (≤3%)
4 mm²32 A25 A1.48 V (0.37%)398.5 V2.45 V (0.61%)41.1 W✓ OK (≤3%)
6 mm²41 A32 A0.99 V (0.25%)399.0 V1.63 V (0.41%)27.4 W✓ OK (≤3%)
10 mm²57 A44 A0.59 V (0.15%)399.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
16 mm²76 A59 A0.37 V (0.09%)399.6 V0.61 V (0.15%)10.3 W✓ OK (≤3%)
25 mm²101 A78 A0.24 V (0.06%)399.8 V0.39 V (0.1%)6.6 W✓ OK (≤3%)
35 mm²125 A97 A0.17 V (0.04%)399.8 V0.28 V (0.07%)4.7 W✓ OK (≤3%)
50 mm²151 A118 A0.12 V (0.03%)399.9 V0.2 V (0.05%)3.3 W✓ OK (≤3%)
70 mm²192 A150 A0.08 V (0.02%)399.9 V0.14 V (0.03%)2.3 W✓ OK (≤3%)
95 mm²232 A181 A0.06 V (0.02%)399.9 V0.1 V (0.03%)1.7 W✓ OK (≤3%)
120 mm²269 A210 A0.05 V (0.01%)400.0 V0.08 V (0.02%)1.4 W✓ OK (≤3%)
150 mm²309 A241 A0.04 V (0.01%)400.0 V0.07 V (0.02%)1.1 W✓ OK (≤3%)
185 mm²353 A275 A0.03 V (0.01%)400.0 V0.05 V (0.01%)0.9 W✓ OK (≤3%)
240 mm²415 A324 A0.02 V (0.01%)400.0 V0.04 V (0.01%)0.7 W✓ OK (≤3%)
300 mm²477 A372 A0.02 V (0.0%)400.0 V0.03 V (0.01%)0.5 W✓ OK (≤3%)
400 mm²570 A445 A0.01 V (0.0%)400.0 V0.02 V (0.01%)0.4 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 10 Meter (400V)

Vilken kabelarea krävs för 16A vid 10 meter (400V)?

För 16 Ampere över 10 meter vid 400V rekommenderas 1.5 mm² kopparkabel för att hålla spänningsfallet under 3% (3.95V / 0.99%).

Hur stor effekt motsvarar 16A vid 400V?

Det motsvarar 11.09 kW med en rekommenderad säkring på 16A.