Kabelarea för 16 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 16 A över 120 m vid 400V.

Copper Cable (≤3% Drop)6 mm²Drop: 11.86V (2.97%)
Aluminum Cable (≤3% Drop)10 mm²Drop: 11.74V (2.93%)
Voltage at Load388.1 VLine Loss: 328.7 W
Max Power & Breaker11.09 kW16A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 16A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A47.44 V (11.86%)352.6 V78.26 V (19.57%)1314.8 WDrop High
2.5 mm²24 A18 A28.47 V (7.12%)371.5 V46.96 V (11.74%)788.9 WDrop High
4 mm²32 A25 A17.79 V (4.45%)382.2 V29.35 V (7.34%)493.1 W~ ≤5%
6 mm²41 A32 A11.86 V (2.97%)388.1 V19.57 V (4.89%)328.7 W✓ OK (≤3%)
10 mm²57 A44 A7.12 V (1.78%)392.9 V11.74 V (2.93%)197.2 W✓ OK (≤3%)
16 mm²76 A59 A4.45 V (1.11%)395.6 V7.34 V (1.83%)123.3 W✓ OK (≤3%)
25 mm²101 A78 A2.85 V (0.71%)397.2 V4.7 V (1.17%)78.9 W✓ OK (≤3%)
35 mm²125 A97 A2.03 V (0.51%)398.0 V3.35 V (0.84%)56.3 W✓ OK (≤3%)
50 mm²151 A118 A1.42 V (0.36%)398.6 V2.35 V (0.59%)39.4 W✓ OK (≤3%)
70 mm²192 A150 A1.02 V (0.25%)399.0 V1.68 V (0.42%)28.2 W✓ OK (≤3%)
95 mm²232 A181 A0.75 V (0.19%)399.3 V1.24 V (0.31%)20.8 W✓ OK (≤3%)
120 mm²269 A210 A0.59 V (0.15%)399.4 V0.98 V (0.24%)16.4 W✓ OK (≤3%)
150 mm²309 A241 A0.47 V (0.12%)399.5 V0.78 V (0.2%)13.1 W✓ OK (≤3%)
185 mm²353 A275 A0.38 V (0.1%)399.6 V0.63 V (0.16%)10.7 W✓ OK (≤3%)
240 mm²415 A324 A0.3 V (0.07%)399.7 V0.49 V (0.12%)8.2 W✓ OK (≤3%)
300 mm²477 A372 A0.24 V (0.06%)399.8 V0.39 V (0.1%)6.6 W✓ OK (≤3%)
400 mm²570 A445 A0.18 V (0.04%)399.8 V0.29 V (0.07%)4.9 W✓ OK (≤3%)

FAQ — Kabelarea för 16 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 16A vid 120 meter (400V)?

För 16 Ampere över 120 meter vid 400V rekommenderas 6 mm² kopparkabel för att hålla spänningsfallet under 3% (11.86V / 2.97%).

Hur stor effekt motsvarar 16A vid 400V?

Det motsvarar 11.09 kW med en rekommenderad säkring på 16A.