Kabelarea för 32 Ampere vid 120 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 120 m vid 400V.
Copper Cable (≤3% Drop)16 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.39V (2.35%)
Voltage at Load391.1 VLine Loss: 493.1 W
Max Power & Breaker22.17 kW32A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 120m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 94.89 V (23.72%) | 305.1 V | 156.52 V (39.13%) | 5259.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 56.93 V (14.23%) | 343.1 V | 93.91 V (23.48%) | 3155.6 W | Drop High |
| 4 mm² | 32 A | 25 A | 35.58 V (8.9%) | 364.4 V | 58.7 V (14.67%) | 1972.2 W | Drop High |
| 6 mm² | 41 A | 32 A | 23.72 V (5.93%) | 376.3 V | 39.13 V (9.78%) | 1314.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 14.23 V (3.56%) | 385.8 V | 23.48 V (5.87%) | 788.9 W | ~ ≤5% |
| 16 mm² | 76 A | 59 A | 8.9 V (2.22%) | 391.1 V | 14.67 V (3.67%) | 493.1 W | ✓ OK (≤3%) |
| 25 mm² | 101 A | 78 A | 5.69 V (1.42%) | 394.3 V | 9.39 V (2.35%) | 315.6 W | ✓ OK (≤3%) |
| 35 mm² | 125 A | 97 A | 4.07 V (1.02%) | 395.9 V | 6.71 V (1.68%) | 225.4 W | ✓ OK (≤3%) |
| 50 mm² | 151 A | 118 A | 2.85 V (0.71%) | 397.2 V | 4.7 V (1.17%) | 157.8 W | ✓ OK (≤3%) |
| 70 mm² | 192 A | 150 A | 2.03 V (0.51%) | 398.0 V | 3.35 V (0.84%) | 112.7 W | ✓ OK (≤3%) |
| 95 mm² | 232 A | 181 A | 1.5 V (0.37%) | 398.5 V | 2.47 V (0.62%) | 83.0 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.19 V (0.3%) | 398.8 V | 1.96 V (0.49%) | 65.7 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.95 V (0.24%) | 399.1 V | 1.57 V (0.39%) | 52.6 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.77 V (0.19%) | 399.2 V | 1.27 V (0.32%) | 42.6 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.59 V (0.15%) | 399.4 V | 0.98 V (0.24%) | 32.9 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.47 V (0.12%) | 399.5 V | 0.78 V (0.2%) | 26.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.36 V (0.09%) | 399.6 V | 0.59 V (0.15%) | 19.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 32 Ampere vid 120 Meter (400V)
Vilken kabelarea krävs för 32A vid 120 meter (400V)?
För 32 Ampere över 120 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (8.9V / 2.22%).
Hur stor effekt motsvarar 32A vid 400V?
Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.
Related Lengths & Currents (400V)
32A · 5m (400V)32A · 10m (400V)32A · 15m (400V)32A · 20m (400V)32A · 25m (400V)32A · 30m (400V)32A · 35m (400V)32A · 40m (400V)32A · 45m (400V)32A · 50m (400V)32A · 60m (400V)32A · 70m (400V)10A · 120m (400V)16A · 120m (400V)20A · 120m (400V)25A · 120m (400V)40A · 120m (400V)50A · 120m (400V)63A · 120m (400V)80A · 120m (400V)100A · 120m (400V)125A · 120m (400V)160A · 120m (400V)200A · 120m (400V)