Kabelarea för 32 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 32 A över 120 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 9.39V (2.35%)
Voltage at Load391.1 VLine Loss: 493.1 W
Max Power & Breaker22.17 kW32A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 32A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A94.89 V (23.72%)305.1 V156.52 V (39.13%)5259.3 WDrop High
2.5 mm²24 A18 A56.93 V (14.23%)343.1 V93.91 V (23.48%)3155.6 WDrop High
4 mm²32 A25 A35.58 V (8.9%)364.4 V58.7 V (14.67%)1972.2 WDrop High
6 mm²41 A32 A23.72 V (5.93%)376.3 V39.13 V (9.78%)1314.8 WDrop High
10 mm²57 A44 A14.23 V (3.56%)385.8 V23.48 V (5.87%)788.9 W~ ≤5%
16 mm²76 A59 A8.9 V (2.22%)391.1 V14.67 V (3.67%)493.1 W✓ OK (≤3%)
25 mm²101 A78 A5.69 V (1.42%)394.3 V9.39 V (2.35%)315.6 W✓ OK (≤3%)
35 mm²125 A97 A4.07 V (1.02%)395.9 V6.71 V (1.68%)225.4 W✓ OK (≤3%)
50 mm²151 A118 A2.85 V (0.71%)397.2 V4.7 V (1.17%)157.8 W✓ OK (≤3%)
70 mm²192 A150 A2.03 V (0.51%)398.0 V3.35 V (0.84%)112.7 W✓ OK (≤3%)
95 mm²232 A181 A1.5 V (0.37%)398.5 V2.47 V (0.62%)83.0 W✓ OK (≤3%)
120 mm²269 A210 A1.19 V (0.3%)398.8 V1.96 V (0.49%)65.7 W✓ OK (≤3%)
150 mm²309 A241 A0.95 V (0.24%)399.1 V1.57 V (0.39%)52.6 W✓ OK (≤3%)
185 mm²353 A275 A0.77 V (0.19%)399.2 V1.27 V (0.32%)42.6 W✓ OK (≤3%)
240 mm²415 A324 A0.59 V (0.15%)399.4 V0.98 V (0.24%)32.9 W✓ OK (≤3%)
300 mm²477 A372 A0.47 V (0.12%)399.5 V0.78 V (0.2%)26.3 W✓ OK (≤3%)
400 mm²570 A445 A0.36 V (0.09%)399.6 V0.59 V (0.15%)19.7 W✓ OK (≤3%)

FAQ — Kabelarea för 32 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 32A vid 120 meter (400V)?

För 32 Ampere över 120 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (8.9V / 2.22%).

Hur stor effekt motsvarar 32A vid 400V?

Det motsvarar 22.17 kW med en rekommenderad säkring på 32A.