Kabelarea för 20 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 20 A över 120 m vid 400V.

Copper Cable (≤3% Drop)10 mm²Drop: 8.9V (2.22%)
Aluminum Cable (≤3% Drop)16 mm²Drop: 9.17V (2.29%)
Voltage at Load391.1 VLine Loss: 308.2 W
Max Power & Breaker13.86 kW20A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 20A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A59.31 V (14.83%)340.7 V97.83 V (24.46%)2054.4 WDrop High
2.5 mm²24 A18 A35.58 V (8.9%)364.4 V58.7 V (14.67%)1232.6 WDrop High
4 mm²32 A25 A22.24 V (5.56%)377.8 V36.68 V (9.17%)770.4 WDrop High
6 mm²41 A32 A14.83 V (3.71%)385.2 V24.46 V (6.11%)513.6 W~ ≤5%
10 mm²57 A44 A8.9 V (2.22%)391.1 V14.67 V (3.67%)308.2 W✓ OK (≤3%)
16 mm²76 A59 A5.56 V (1.39%)394.4 V9.17 V (2.29%)192.6 W✓ OK (≤3%)
25 mm²101 A78 A3.56 V (0.89%)396.4 V5.87 V (1.47%)123.3 W✓ OK (≤3%)
35 mm²125 A97 A2.54 V (0.64%)397.5 V4.19 V (1.05%)88.0 W✓ OK (≤3%)
50 mm²151 A118 A1.78 V (0.44%)398.2 V2.93 V (0.73%)61.6 W✓ OK (≤3%)
70 mm²192 A150 A1.27 V (0.32%)398.7 V2.1 V (0.52%)44.0 W✓ OK (≤3%)
95 mm²232 A181 A0.94 V (0.23%)399.1 V1.54 V (0.39%)32.4 W✓ OK (≤3%)
120 mm²269 A210 A0.74 V (0.19%)399.3 V1.22 V (0.31%)25.7 W✓ OK (≤3%)
150 mm²309 A241 A0.59 V (0.15%)399.4 V0.98 V (0.24%)20.5 W✓ OK (≤3%)
185 mm²353 A275 A0.48 V (0.12%)399.5 V0.79 V (0.2%)16.7 W✓ OK (≤3%)
240 mm²415 A324 A0.37 V (0.09%)399.6 V0.61 V (0.15%)12.8 W✓ OK (≤3%)
300 mm²477 A372 A0.3 V (0.07%)399.7 V0.49 V (0.12%)10.3 W✓ OK (≤3%)
400 mm²570 A445 A0.22 V (0.06%)399.8 V0.37 V (0.09%)7.7 W✓ OK (≤3%)

FAQ — Kabelarea för 20 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 20A vid 120 meter (400V)?

För 20 Ampere över 120 meter vid 400V rekommenderas 10 mm² kopparkabel för att hålla spänningsfallet under 3% (8.9V / 2.22%).

Hur stor effekt motsvarar 20A vid 400V?

Det motsvarar 13.86 kW med en rekommenderad säkring på 20A.