Kabelarea för 63 Ampere vid 120 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 63 A över 120 m vid 400V.

Copper Cable (≤3% Drop)25 mm²Drop: 11.21V (2.8%)
Aluminum Cable (≤3% Drop)50 mm²Drop: 9.24V (2.31%)
Voltage at Load388.8 VLine Loss: 1223.1 W
Max Power & Breaker43.65 kW63A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 63A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A186.81 V (46.7%)213.2 V308.15 V (77.04%)20384.8 WDrop High
2.5 mm²24 A18 A112.09 V (28.02%)287.9 V184.89 V (46.22%)12230.9 WDrop High
4 mm²32 A25 A70.05 V (17.51%)329.9 V115.56 V (28.89%)7644.3 WDrop High
6 mm²41 A32 A46.7 V (11.68%)353.3 V77.04 V (19.26%)5096.2 WDrop High
10 mm²57 A44 A28.02 V (7.01%)372.0 V46.22 V (11.56%)3057.7 WDrop High
16 mm²76 A59 A17.51 V (4.38%)382.5 V28.89 V (7.22%)1911.1 W~ ≤5%
25 mm²101 A78 A11.21 V (2.8%)388.8 V18.49 V (4.62%)1223.1 W✓ OK (≤3%)
35 mm²125 A97 A8.01 V (2.0%)392.0 V13.21 V (3.3%)873.6 W✓ OK (≤3%)
50 mm²151 A118 A5.6 V (1.4%)394.4 V9.24 V (2.31%)611.5 W✓ OK (≤3%)
70 mm²192 A150 A4.0 V (1.0%)396.0 V6.6 V (1.65%)436.8 W✓ OK (≤3%)
95 mm²232 A181 A2.95 V (0.74%)397.1 V4.87 V (1.22%)321.9 W✓ OK (≤3%)
120 mm²269 A210 A2.34 V (0.58%)397.7 V3.85 V (0.96%)254.8 W✓ OK (≤3%)
150 mm²309 A241 A1.87 V (0.47%)398.1 V3.08 V (0.77%)203.8 W✓ OK (≤3%)
185 mm²353 A275 A1.51 V (0.38%)398.5 V2.5 V (0.62%)165.3 W✓ OK (≤3%)
240 mm²415 A324 A1.17 V (0.29%)398.8 V1.93 V (0.48%)127.4 W✓ OK (≤3%)
300 mm²477 A372 A0.93 V (0.23%)399.1 V1.54 V (0.39%)101.9 W✓ OK (≤3%)
400 mm²570 A445 A0.7 V (0.18%)399.3 V1.16 V (0.29%)76.4 W✓ OK (≤3%)

FAQ — Kabelarea för 63 Ampere vid 120 Meter (400V)

Vilken kabelarea krävs för 63A vid 120 meter (400V)?

För 63 Ampere över 120 meter vid 400V rekommenderas 25 mm² kopparkabel för att hålla spänningsfallet under 3% (11.21V / 2.8%).

Hur stor effekt motsvarar 63A vid 400V?

Det motsvarar 43.65 kW med en rekommenderad säkring på 63A.