Kabelarea för 225 Ampere vid 15 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 15 m vid 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 1.32V (0.33%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.38V (0.34%)
Voltage at Load398.7 VLine Loss: 513.2 W
Max Power & Breaker155.88 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 15m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A83.4 V (20.85%)316.6 V137.57 V (34.39%)32501.2 WDrop High
2.5 mm²24 A18 A50.04 V (12.51%)350.0 V82.54 V (20.64%)19500.8 WDrop High
4 mm²32 A25 A31.27 V (7.82%)368.7 V51.59 V (12.9%)12188.0 WDrop High
6 mm²41 A32 A20.85 V (5.21%)379.2 V34.39 V (8.6%)8125.3 WDrop High
10 mm²57 A44 A12.51 V (3.13%)387.5 V20.64 V (5.16%)4875.2 WDrop High
16 mm²76 A59 A7.82 V (1.95%)392.2 V12.9 V (3.22%)3047.0 WDrop High
25 mm²101 A78 A5.0 V (1.25%)395.0 V8.25 V (2.06%)1950.1 WDrop High
35 mm²125 A97 A3.57 V (0.89%)396.4 V5.9 V (1.47%)1392.9 WDrop High
50 mm²151 A118 A2.5 V (0.63%)397.5 V4.13 V (1.03%)975.0 WDrop High
70 mm²192 A150 A1.79 V (0.45%)398.2 V2.95 V (0.74%)696.5 WDrop High
95 mm²232 A181 A1.32 V (0.33%)398.7 V2.17 V (0.54%)513.2 W✓ OK (≤3%)
120 mm²269 A210 A1.04 V (0.26%)399.0 V1.72 V (0.43%)406.3 W✓ OK (≤3%)
150 mm²309 A241 A0.83 V (0.21%)399.2 V1.38 V (0.34%)325.0 W✓ OK (≤3%)
185 mm²353 A275 A0.68 V (0.17%)399.3 V1.12 V (0.28%)263.5 W✓ OK (≤3%)
240 mm²415 A324 A0.52 V (0.13%)399.5 V0.86 V (0.21%)203.1 W✓ OK (≤3%)
300 mm²477 A372 A0.42 V (0.1%)399.6 V0.69 V (0.17%)162.5 W✓ OK (≤3%)
400 mm²570 A445 A0.31 V (0.08%)399.7 V0.52 V (0.13%)121.9 W✓ OK (≤3%)

FAQ — Kabelarea för 225 Ampere vid 15 Meter (400V)

Vilken kabelarea krävs för 225A vid 15 meter (400V)?

För 225 Ampere över 15 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (1.32V / 0.33%).

Hur stor effekt motsvarar 225A vid 400V?

Det motsvarar 155.88 kW med en rekommenderad säkring på 225A.