Kabelarea för 225 Ampere vid 15 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 15 m vid 400V.
Copper Cable (≤3% Drop)95 mm²Drop: 1.32V (0.33%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 1.38V (0.34%)
Voltage at Load398.7 VLine Loss: 513.2 W
Max Power & Breaker155.88 kW225A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 15m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 83.4 V (20.85%) | 316.6 V | 137.57 V (34.39%) | 32501.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 50.04 V (12.51%) | 350.0 V | 82.54 V (20.64%) | 19500.8 W | Drop High |
| 4 mm² | 32 A | 25 A | 31.27 V (7.82%) | 368.7 V | 51.59 V (12.9%) | 12188.0 W | Drop High |
| 6 mm² | 41 A | 32 A | 20.85 V (5.21%) | 379.2 V | 34.39 V (8.6%) | 8125.3 W | Drop High |
| 10 mm² | 57 A | 44 A | 12.51 V (3.13%) | 387.5 V | 20.64 V (5.16%) | 4875.2 W | Drop High |
| 16 mm² | 76 A | 59 A | 7.82 V (1.95%) | 392.2 V | 12.9 V (3.22%) | 3047.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 5.0 V (1.25%) | 395.0 V | 8.25 V (2.06%) | 1950.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 3.57 V (0.89%) | 396.4 V | 5.9 V (1.47%) | 1392.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 2.5 V (0.63%) | 397.5 V | 4.13 V (1.03%) | 975.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 1.79 V (0.45%) | 398.2 V | 2.95 V (0.74%) | 696.5 W | Drop High |
| 95 mm² | 232 A | 181 A | 1.32 V (0.33%) | 398.7 V | 2.17 V (0.54%) | 513.2 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 1.04 V (0.26%) | 399.0 V | 1.72 V (0.43%) | 406.3 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.83 V (0.21%) | 399.2 V | 1.38 V (0.34%) | 325.0 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.68 V (0.17%) | 399.3 V | 1.12 V (0.28%) | 263.5 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.52 V (0.13%) | 399.5 V | 0.86 V (0.21%) | 203.1 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.42 V (0.1%) | 399.6 V | 0.69 V (0.17%) | 162.5 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.31 V (0.08%) | 399.7 V | 0.52 V (0.13%) | 121.9 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 225 Ampere vid 15 Meter (400V)
Vilken kabelarea krävs för 225A vid 15 meter (400V)?
För 225 Ampere över 15 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (1.32V / 0.33%).
Hur stor effekt motsvarar 225A vid 400V?
Det motsvarar 155.88 kW med en rekommenderad säkring på 225A.
Related Lengths & Currents (400V)
225A · 5m (400V)225A · 10m (400V)225A · 20m (400V)225A · 25m (400V)225A · 30m (400V)225A · 35m (400V)225A · 40m (400V)225A · 45m (400V)225A · 50m (400V)225A · 60m (400V)225A · 70m (400V)10A · 15m (400V)16A · 15m (400V)20A · 15m (400V)25A · 15m (400V)32A · 15m (400V)40A · 15m (400V)50A · 15m (400V)63A · 15m (400V)80A · 15m (400V)100A · 15m (400V)125A · 15m (400V)160A · 15m (400V)200A · 15m (400V)