⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 225 Ampere vid 35 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 35 m vid 400V.

Copper Cable (≤3% Drop)95 mm²Drop: 3.07V (0.77%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 3.21V (0.8%)
Voltage at Load396.9 VLine Loss: 1197.4 W
Max Power & Breaker155.88 kW225A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A194.6 V (48.65%)205.4 V320.99 V (80.25%)75836.2 WDrop High
2.5 mm²24 A18 A116.76 V (29.19%)283.2 V192.6 V (48.15%)45501.8 WDrop High
4 mm²32 A25 A72.97 V (18.24%)327.0 V120.37 V (30.09%)28438.6 WDrop High
6 mm²41 A32 A48.65 V (12.16%)351.4 V80.25 V (20.06%)18959.1 WDrop High
10 mm²57 A44 A29.19 V (7.3%)370.8 V48.15 V (12.04%)11375.4 WDrop High
16 mm²76 A59 A18.24 V (4.56%)381.8 V30.09 V (7.52%)7109.6 WDrop High
25 mm²101 A78 A11.68 V (2.92%)388.3 V19.26 V (4.81%)4550.2 WDrop High
35 mm²125 A97 A8.34 V (2.08%)391.7 V13.76 V (3.44%)3250.1 WDrop High
50 mm²151 A118 A5.84 V (1.46%)394.2 V9.63 V (2.41%)2275.1 WDrop High
70 mm²192 A150 A4.17 V (1.04%)395.8 V6.88 V (1.72%)1625.1 WDrop High
95 mm²232 A181 A3.07 V (0.77%)396.9 V5.07 V (1.27%)1197.4 W✓ OK (≤3%)
120 mm²269 A210 A2.43 V (0.61%)397.6 V4.01 V (1.0%)948.0 W✓ OK (≤3%)
150 mm²309 A241 A1.95 V (0.49%)398.1 V3.21 V (0.8%)758.4 W✓ OK (≤3%)
185 mm²353 A275 A1.58 V (0.39%)398.4 V2.6 V (0.65%)614.9 W✓ OK (≤3%)
240 mm²415 A324 A1.22 V (0.3%)398.8 V2.01 V (0.5%)474.0 W✓ OK (≤3%)
300 mm²477 A372 A0.97 V (0.24%)399.0 V1.6 V (0.4%)379.2 W✓ OK (≤3%)
400 mm²570 A445 A0.73 V (0.18%)399.3 V1.2 V (0.3%)284.4 W✓ OK (≤3%)

FAQ — Kabelarea för 225 Ampere vid 35 Meter (400V)

Vilken kabelarea krävs för 225A vid 35 meter (400V)?

För 225 Ampere över 35 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (3.07V / 0.77%).

Hur stor effekt motsvarar 225A vid 400V?

Det motsvarar 155.88 kW med en rekommenderad säkring på 225A.