Kabelarea för 225 Ampere vid 10 Meter (400V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 225 A över 10 m vid 400V.
Copper Cable (≤3% Drop)95 mm²Drop: 0.88V (0.22%)
Aluminum Cable (≤3% Drop)150 mm²Drop: 0.92V (0.23%)
Voltage at Load399.1 VLine Loss: 342.1 W
Max Power & Breaker155.88 kW225A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 225A at 10m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 55.6 V (13.9%) | 344.4 V | 91.71 V (22.93%) | 21667.5 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 33.36 V (8.34%) | 366.6 V | 55.03 V (13.76%) | 13000.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 20.85 V (5.21%) | 379.2 V | 34.39 V (8.6%) | 8125.3 W | Drop High |
| 6 mm² | 41 A | 32 A | 13.9 V (3.47%) | 386.1 V | 22.93 V (5.73%) | 5416.9 W | Drop High |
| 10 mm² | 57 A | 44 A | 8.34 V (2.08%) | 391.7 V | 13.76 V (3.44%) | 3250.1 W | Drop High |
| 16 mm² | 76 A | 59 A | 5.21 V (1.3%) | 394.8 V | 8.6 V (2.15%) | 2031.3 W | Drop High |
| 25 mm² | 101 A | 78 A | 3.34 V (0.83%) | 396.7 V | 5.5 V (1.38%) | 1300.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 2.38 V (0.6%) | 397.6 V | 3.93 V (0.98%) | 928.6 W | Drop High |
| 50 mm² | 151 A | 118 A | 1.67 V (0.42%) | 398.3 V | 2.75 V (0.69%) | 650.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 1.19 V (0.3%) | 398.8 V | 1.97 V (0.49%) | 464.3 W | Drop High |
| 95 mm² | 232 A | 181 A | 0.88 V (0.22%) | 399.1 V | 1.45 V (0.36%) | 342.1 W | ✓ OK (≤3%) |
| 120 mm² | 269 A | 210 A | 0.69 V (0.17%) | 399.3 V | 1.15 V (0.29%) | 270.8 W | ✓ OK (≤3%) |
| 150 mm² | 309 A | 241 A | 0.56 V (0.14%) | 399.4 V | 0.92 V (0.23%) | 216.7 W | ✓ OK (≤3%) |
| 185 mm² | 353 A | 275 A | 0.45 V (0.11%) | 399.5 V | 0.74 V (0.19%) | 175.7 W | ✓ OK (≤3%) |
| 240 mm² | 415 A | 324 A | 0.35 V (0.09%) | 399.7 V | 0.57 V (0.14%) | 135.4 W | ✓ OK (≤3%) |
| 300 mm² | 477 A | 372 A | 0.28 V (0.07%) | 399.7 V | 0.46 V (0.11%) | 108.3 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 0.21 V (0.05%) | 399.8 V | 0.34 V (0.09%) | 81.3 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 225 Ampere vid 10 Meter (400V)
Vilken kabelarea krävs för 225A vid 10 meter (400V)?
För 225 Ampere över 10 meter vid 400V rekommenderas 95 mm² kopparkabel för att hålla spänningsfallet under 3% (0.88V / 0.22%).
Hur stor effekt motsvarar 225A vid 400V?
Det motsvarar 155.88 kW med en rekommenderad säkring på 225A.
Related Lengths & Currents (400V)
225A · 5m (400V)225A · 15m (400V)225A · 20m (400V)225A · 25m (400V)225A · 30m (400V)225A · 35m (400V)225A · 40m (400V)225A · 45m (400V)225A · 50m (400V)225A · 60m (400V)225A · 70m (400V)10A · 10m (400V)16A · 10m (400V)20A · 10m (400V)25A · 10m (400V)32A · 10m (400V)40A · 10m (400V)50A · 10m (400V)63A · 10m (400V)80A · 10m (400V)100A · 10m (400V)125A · 10m (400V)160A · 10m (400V)200A · 10m (400V)