Kabelarea för 275 Ampere vid 600 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 275 A över 600 m vid 230V.
Copper Cable (≤3% Drop)3× 400 mm²Drop: 5.88V (2.56%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 29.12V (12.66%)
Voltage at Load224.1 VLine Loss: 1618.4 W
Max Power & Breaker63.25 kW300A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 275A at 600m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 4708.0 V (2046.96%) | 0.0 V | 7766.0 V (3376.52%) | 1294700.0 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 2824.8 V (1228.17%) | 0.0 V | 4659.6 V (2025.91%) | 776820.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 1765.5 V (767.61%) | 0.0 V | 2912.25 V (1266.2%) | 485512.5 W | Drop High |
| 6 mm² | 41 A | 32 A | 1177.0 V (511.74%) | 0.0 V | 1941.5 V (844.13%) | 323675.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 706.2 V (307.04%) | 0.0 V | 1164.9 V (506.48%) | 194205.0 W | Drop High |
| 16 mm² | 76 A | 59 A | 441.38 V (191.9%) | 0.0 V | 728.06 V (316.55%) | 121378.1 W | Drop High |
| 25 mm² | 101 A | 78 A | 282.48 V (122.82%) | 0.0 V | 465.96 V (202.59%) | 77682.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 201.77 V (87.73%) | 28.2 V | 332.83 V (144.71%) | 55487.1 W | Drop High |
| 50 mm² | 151 A | 118 A | 141.24 V (61.41%) | 88.8 V | 232.98 V (101.3%) | 38841.0 W | Drop High |
| 70 mm² | 192 A | 150 A | 100.89 V (43.86%) | 129.1 V | 166.41 V (72.35%) | 27743.6 W | Drop High |
| 95 mm² | 232 A | 181 A | 74.34 V (32.32%) | 155.7 V | 122.62 V (53.31%) | 20442.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 58.85 V (25.59%) | 171.2 V | 97.07 V (42.21%) | 16183.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 47.08 V (20.47%) | 182.9 V | 77.66 V (33.77%) | 12947.0 W | Drop High |
| 185 mm² | 353 A | 275 A | 38.17 V (16.6%) | 191.8 V | 62.97 V (27.38%) | 10497.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 29.43 V (12.79%) | 200.6 V | 48.54 V (21.1%) | 8091.9 W | Drop High |
| 300 mm² | 477 A | 372 A | 23.54 V (10.23%) | 206.5 V | 38.83 V (16.88%) | 6473.5 W | Drop High |
| 400 mm² | 570 A | 445 A | 17.65 V (7.68%) | 212.3 V | 29.12 V (12.66%) | 4855.1 W | Drop High |
FAQ — Kabelarea för 275 Ampere vid 600 Meter (230V)
Vilken kabelarea krävs för 275A vid 600 meter (230V)?
För 275 Ampere över 600 meter vid 230V rekommenderas 3× 400 mm² kopparkabel för att hålla spänningsfallet under 3% (5.88V / 2.56%).
Hur stor effekt motsvarar 275A vid 230V?
Det motsvarar 63.25 kW med en rekommenderad säkring på 300A.
Related Lengths & Currents (230V)
275A · 5m (230V)275A · 10m (230V)275A · 15m (230V)275A · 20m (230V)275A · 25m (230V)275A · 30m (230V)275A · 35m (230V)275A · 40m (230V)275A · 45m (230V)275A · 50m (230V)275A · 60m (230V)275A · 70m (230V)10A · 600m (230V)16A · 600m (230V)20A · 600m (230V)25A · 600m (230V)32A · 600m (230V)40A · 600m (230V)50A · 600m (230V)63A · 600m (230V)80A · 600m (230V)100A · 600m (230V)125A · 600m (230V)160A · 600m (230V)200A · 600m (230V)