Kabelarea för 30 Ampere vid 150 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 30 A över 150 m vid 400V.

Copper Cable (≤3% Drop)16 mm²Drop: 10.42V (2.61%)
Aluminum Cable (≤3% Drop)25 mm²Drop: 11.01V (2.75%)
Voltage at Load389.6 VLine Loss: 541.7 W
Max Power & Breaker20.78 kW30A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 30A at 150m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A111.2 V (27.8%)288.8 V183.42 V (45.86%)5778.0 WDrop High
2.5 mm²24 A18 A66.72 V (16.68%)333.3 V110.05 V (27.51%)3466.8 WDrop High
4 mm²32 A25 A41.7 V (10.42%)358.3 V68.78 V (17.2%)2166.8 WDrop High
6 mm²41 A32 A27.8 V (6.95%)372.2 V45.86 V (11.46%)1444.5 WDrop High
10 mm²57 A44 A16.68 V (4.17%)383.3 V27.51 V (6.88%)866.7 W~ ≤5%
16 mm²76 A59 A10.42 V (2.61%)389.6 V17.2 V (4.3%)541.7 W✓ OK (≤3%)
25 mm²101 A78 A6.67 V (1.67%)393.3 V11.01 V (2.75%)346.7 W✓ OK (≤3%)
35 mm²125 A97 A4.77 V (1.19%)395.2 V7.86 V (1.97%)247.6 W✓ OK (≤3%)
50 mm²151 A118 A3.34 V (0.83%)396.7 V5.5 V (1.38%)173.3 W✓ OK (≤3%)
70 mm²192 A150 A2.38 V (0.6%)397.6 V3.93 V (0.98%)123.8 W✓ OK (≤3%)
95 mm²232 A181 A1.76 V (0.44%)398.2 V2.9 V (0.72%)91.2 W✓ OK (≤3%)
120 mm²269 A210 A1.39 V (0.35%)398.6 V2.29 V (0.57%)72.2 W✓ OK (≤3%)
150 mm²309 A241 A1.11 V (0.28%)398.9 V1.83 V (0.46%)57.8 W✓ OK (≤3%)
185 mm²353 A275 A0.9 V (0.23%)399.1 V1.49 V (0.37%)46.8 W✓ OK (≤3%)
240 mm²415 A324 A0.69 V (0.17%)399.3 V1.15 V (0.29%)36.1 W✓ OK (≤3%)
300 mm²477 A372 A0.56 V (0.14%)399.4 V0.92 V (0.23%)28.9 W✓ OK (≤3%)
400 mm²570 A445 A0.42 V (0.1%)399.6 V0.69 V (0.17%)21.7 W✓ OK (≤3%)

FAQ — Kabelarea för 30 Ampere vid 150 Meter (400V)

Vilken kabelarea krävs för 30A vid 150 meter (400V)?

För 30 Ampere över 150 meter vid 400V rekommenderas 16 mm² kopparkabel för att hålla spänningsfallet under 3% (10.42V / 2.61%).

Hur stor effekt motsvarar 30A vid 400V?

Det motsvarar 20.78 kW med en rekommenderad säkring på 30A.