Kabelarea för 325 Ampere vid 80 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 325 A över 80 m vid 400V.

Copper Cable (≤3% Drop)185 mm²Drop: 5.21V (1.3%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 5.3V (1.32%)
Voltage at Load394.8 VLine Loss: 2932.4 W
Max Power & Breaker225.17 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A642.48 V (160.62%)0.0 V1059.78 V (264.95%)361660.0 WDrop High
2.5 mm²24 A18 A385.49 V (96.37%)14.5 V635.87 V (158.97%)216996.0 WDrop High
4 mm²32 A25 A240.93 V (60.23%)159.1 V397.42 V (99.35%)135622.5 WDrop High
6 mm²41 A32 A160.62 V (40.15%)239.4 V264.95 V (66.24%)90415.0 WDrop High
10 mm²57 A44 A96.37 V (24.09%)303.6 V158.97 V (39.74%)54249.0 WDrop High
16 mm²76 A59 A60.23 V (15.06%)339.8 V99.35 V (24.84%)33905.6 WDrop High
25 mm²101 A78 A38.55 V (9.64%)361.5 V63.59 V (15.9%)21699.6 WDrop High
35 mm²125 A97 A27.53 V (6.88%)372.5 V45.42 V (11.35%)15499.7 WDrop High
50 mm²151 A118 A19.27 V (4.82%)380.7 V31.79 V (7.95%)10849.8 WDrop High
70 mm²192 A150 A13.77 V (3.44%)386.2 V22.71 V (5.68%)7749.9 WDrop High
95 mm²232 A181 A10.14 V (2.54%)389.9 V16.73 V (4.18%)5710.4 WDrop High
120 mm²269 A210 A8.03 V (2.01%)392.0 V13.25 V (3.31%)4520.8 WDrop High
150 mm²309 A241 A6.42 V (1.61%)393.6 V10.6 V (2.65%)3616.6 WDrop High
185 mm²353 A275 A5.21 V (1.3%)394.8 V8.59 V (2.15%)2932.4 W✓ OK (≤3%)
240 mm²415 A324 A4.02 V (1.0%)396.0 V6.62 V (1.66%)2260.4 W✓ OK (≤3%)
300 mm²477 A372 A3.21 V (0.8%)396.8 V5.3 V (1.32%)1808.3 W✓ OK (≤3%)
400 mm²570 A445 A2.41 V (0.6%)397.6 V3.97 V (0.99%)1356.2 W✓ OK (≤3%)

FAQ — Kabelarea för 325 Ampere vid 80 Meter (400V)

Vilken kabelarea krävs för 325A vid 80 meter (400V)?

För 325 Ampere över 80 meter vid 400V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (5.21V / 1.3%).

Hur stor effekt motsvarar 325A vid 400V?

Det motsvarar 225.17 kW med en rekommenderad säkring på 350A.