Kabelarea för 325 Ampere vid 90 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 325 A över 90 m vid 230V.

Copper Cable (≤3% Drop)185 mm²Drop: 6.77V (2.94%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 6.88V (2.99%)
Voltage at Load223.2 VLine Loss: 2199.3 W
Max Power & Breaker74.75 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A834.6 V (362.87%)0.0 V1376.7 V (598.57%)271245.0 WDrop High
2.5 mm²24 A18 A500.76 V (217.72%)0.0 V826.02 V (359.14%)162747.0 WDrop High
4 mm²32 A25 A312.97 V (136.08%)0.0 V516.26 V (224.46%)101716.9 WDrop High
6 mm²41 A32 A208.65 V (90.72%)21.3 V344.17 V (149.64%)67811.2 WDrop High
10 mm²57 A44 A125.19 V (54.43%)104.8 V206.5 V (89.78%)40686.8 WDrop High
16 mm²76 A59 A78.24 V (34.02%)151.8 V129.07 V (56.12%)25429.2 WDrop High
25 mm²101 A78 A50.08 V (21.77%)179.9 V82.6 V (35.91%)16274.7 WDrop High
35 mm²125 A97 A35.77 V (15.55%)194.2 V59.0 V (25.65%)11624.8 WDrop High
50 mm²151 A118 A25.04 V (10.89%)205.0 V41.3 V (17.96%)8137.3 WDrop High
70 mm²192 A150 A17.88 V (7.78%)212.1 V29.5 V (12.83%)5812.4 WDrop High
95 mm²232 A181 A13.18 V (5.73%)216.8 V21.74 V (9.45%)4282.8 WDrop High
120 mm²269 A210 A10.43 V (4.54%)219.6 V17.21 V (7.48%)3390.6 WDrop High
150 mm²309 A241 A8.35 V (3.63%)221.7 V13.77 V (5.99%)2712.4 WDrop High
185 mm²353 A275 A6.77 V (2.94%)223.2 V11.16 V (4.85%)2199.3 W✓ OK (≤3%)
240 mm²415 A324 A5.22 V (2.27%)224.8 V8.6 V (3.74%)1695.3 W✓ OK (≤3%)
300 mm²477 A372 A4.17 V (1.81%)225.8 V6.88 V (2.99%)1356.2 W✓ OK (≤3%)
400 mm²570 A445 A3.13 V (1.36%)226.9 V5.16 V (2.24%)1017.2 W✓ OK (≤3%)

FAQ — Kabelarea för 325 Ampere vid 90 Meter (230V)

Vilken kabelarea krävs för 325A vid 90 meter (230V)?

För 325 Ampere över 90 meter vid 230V rekommenderas 185 mm² kopparkabel för att hålla spänningsfallet under 3% (6.77V / 2.94%).

Hur stor effekt motsvarar 325A vid 230V?

Det motsvarar 74.75 kW med en rekommenderad säkring på 350A.