Kabelarea för 375 Ampere vid 250 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 375 A över 250 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 11.58V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.33V (3.58%)
Voltage at Load388.4 VLine Loss: 7523.4 W
Max Power & Breaker259.81 kW400A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 375A at 250m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2316.62 V (579.15%)0.0 V3821.34 V (955.33%)1504687.5 WDrop High
2.5 mm²24 A18 A1389.97 V (347.49%)0.0 V2292.8 V (573.2%)902812.5 WDrop High
4 mm²32 A25 A868.73 V (217.18%)0.0 V1433.0 V (358.25%)564257.8 WDrop High
6 mm²41 A32 A579.15 V (144.79%)0.0 V955.33 V (238.83%)376171.9 WDrop High
10 mm²57 A44 A347.49 V (86.87%)52.5 V573.2 V (143.3%)225703.1 WDrop High
16 mm²76 A59 A217.18 V (54.3%)182.8 V358.25 V (89.56%)141064.5 WDrop High
25 mm²101 A78 A139.0 V (34.75%)261.0 V229.28 V (57.32%)90281.2 WDrop High
35 mm²125 A97 A99.28 V (24.82%)300.7 V163.77 V (40.94%)64486.6 WDrop High
50 mm²151 A118 A69.5 V (17.37%)330.5 V114.64 V (28.66%)45140.6 WDrop High
70 mm²192 A150 A49.64 V (12.41%)350.4 V81.89 V (20.47%)32243.3 WDrop High
95 mm²232 A181 A36.58 V (9.14%)363.4 V60.34 V (15.08%)23758.2 WDrop High
120 mm²269 A210 A28.96 V (7.24%)371.0 V47.77 V (11.94%)18808.6 WDrop High
150 mm²309 A241 A23.17 V (5.79%)376.8 V38.21 V (9.55%)15046.9 WDrop High
185 mm²353 A275 A18.78 V (4.7%)381.2 V30.98 V (7.75%)12200.2 WDrop High
240 mm²415 A324 A14.48 V (3.62%)385.5 V23.88 V (5.97%)9404.3 W~ ≤5%
300 mm²477 A372 A11.58 V (2.9%)388.4 V19.11 V (4.78%)7523.4 W✓ OK (≤3%)
400 mm²570 A445 A8.69 V (2.17%)391.3 V14.33 V (3.58%)5642.6 W✓ OK (≤3%)

FAQ — Kabelarea för 375 Ampere vid 250 Meter (400V)

Vilken kabelarea krävs för 375A vid 250 meter (400V)?

För 375 Ampere över 250 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (11.58V / 2.9%).

Hur stor effekt motsvarar 375A vid 400V?

Det motsvarar 259.81 kW med en rekommenderad säkring på 400A.