Kabelarea för 425 Ampere vid 100 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 100 m vid 230V.
Copper Cable (≤3% Drop)300 mm²Drop: 6.06V (2.64%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 7.5V (3.26%)
Voltage at Load223.9 VLine Loss: 2576.9 W
Max Power & Breaker97.75 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 100m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 1212.67 V (527.25%) | 0.0 V | 2000.33 V (869.71%) | 515383.3 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 727.6 V (316.35%) | 0.0 V | 1200.2 V (521.83%) | 309230.0 W | Drop High |
| 4 mm² | 32 A | 25 A | 454.75 V (197.72%) | 0.0 V | 750.12 V (326.14%) | 193268.7 W | Drop High |
| 6 mm² | 41 A | 32 A | 303.17 V (131.81%) | 0.0 V | 500.08 V (217.43%) | 128845.8 W | Drop High |
| 10 mm² | 57 A | 44 A | 181.9 V (79.09%) | 48.1 V | 300.05 V (130.46%) | 77307.5 W | Drop High |
| 16 mm² | 76 A | 59 A | 113.69 V (49.43%) | 116.3 V | 187.53 V (81.54%) | 48317.2 W | Drop High |
| 25 mm² | 101 A | 78 A | 72.76 V (31.63%) | 157.2 V | 120.02 V (52.18%) | 30923.0 W | Drop High |
| 35 mm² | 125 A | 97 A | 51.97 V (22.6%) | 178.0 V | 85.73 V (37.27%) | 22087.9 W | Drop High |
| 50 mm² | 151 A | 118 A | 36.38 V (15.82%) | 193.6 V | 60.01 V (26.09%) | 15461.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 25.99 V (11.3%) | 204.0 V | 42.86 V (18.64%) | 11043.9 W | Drop High |
| 95 mm² | 232 A | 181 A | 19.15 V (8.32%) | 210.9 V | 31.58 V (13.73%) | 8137.6 W | Drop High |
| 120 mm² | 269 A | 210 A | 15.16 V (6.59%) | 214.8 V | 25.0 V (10.87%) | 6442.3 W | Drop High |
| 150 mm² | 309 A | 241 A | 12.13 V (5.27%) | 217.9 V | 20.0 V (8.7%) | 5153.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 9.83 V (4.27%) | 220.2 V | 16.22 V (7.05%) | 4178.8 W | Drop High |
| 240 mm² | 415 A | 324 A | 7.58 V (3.3%) | 222.4 V | 12.5 V (5.44%) | 3221.1 W | Drop High |
| 300 mm² | 477 A | 372 A | 6.06 V (2.64%) | 223.9 V | 10.0 V (4.35%) | 2576.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 4.55 V (1.98%) | 225.5 V | 7.5 V (3.26%) | 1932.7 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 425 Ampere vid 100 Meter (230V)
Vilken kabelarea krävs för 425A vid 100 meter (230V)?
För 425 Ampere över 100 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (6.06V / 2.64%).
Hur stor effekt motsvarar 425A vid 230V?
Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.
Related Lengths & Currents (230V)
425A · 5m (230V)425A · 10m (230V)425A · 15m (230V)425A · 20m (230V)425A · 25m (230V)425A · 30m (230V)425A · 35m (230V)425A · 40m (230V)425A · 45m (230V)425A · 50m (230V)425A · 60m (230V)425A · 70m (230V)10A · 100m (230V)16A · 100m (230V)20A · 100m (230V)25A · 100m (230V)32A · 100m (230V)40A · 100m (230V)50A · 100m (230V)63A · 100m (230V)80A · 100m (230V)100A · 100m (230V)125A · 100m (230V)160A · 100m (230V)200A · 100m (230V)