Kabelarea för 425 Ampere vid 35 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 35 m vid 230V.

Copper Cable (≤3% Drop)300 mm²Drop: 2.12V (0.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.63V (1.14%)
Voltage at Load227.9 VLine Loss: 901.9 W
Max Power & Breaker97.75 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 35m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A424.43 V (184.54%)0.0 V700.12 V (304.4%)180384.2 WDrop High
2.5 mm²24 A18 A254.66 V (110.72%)0.0 V420.07 V (182.64%)108230.5 WDrop High
4 mm²32 A25 A159.16 V (69.2%)70.8 V262.54 V (114.15%)67644.1 WDrop High
6 mm²41 A32 A106.11 V (46.13%)123.9 V175.03 V (76.1%)45096.0 WDrop High
10 mm²57 A44 A63.66 V (27.68%)166.3 V105.02 V (45.66%)27057.6 WDrop High
16 mm²76 A59 A39.79 V (17.3%)190.2 V65.64 V (28.54%)16911.0 WDrop High
25 mm²101 A78 A25.47 V (11.07%)204.5 V42.01 V (18.26%)10823.1 WDrop High
35 mm²125 A97 A18.19 V (7.91%)211.8 V30.0 V (13.05%)7730.8 WDrop High
50 mm²151 A118 A12.73 V (5.54%)217.3 V21.0 V (9.13%)5411.5 WDrop High
70 mm²192 A150 A9.09 V (3.95%)220.9 V15.0 V (6.52%)3865.4 WDrop High
95 mm²232 A181 A6.7 V (2.91%)223.3 V11.05 V (4.81%)2848.2 WDrop High
120 mm²269 A210 A5.31 V (2.31%)224.7 V8.75 V (3.8%)2254.8 WDrop High
150 mm²309 A241 A4.24 V (1.85%)225.8 V7.0 V (3.04%)1803.8 WDrop High
185 mm²353 A275 A3.44 V (1.5%)226.6 V5.68 V (2.47%)1462.6 WDrop High
240 mm²415 A324 A2.65 V (1.15%)227.3 V4.38 V (1.9%)1127.4 WDrop High
300 mm²477 A372 A2.12 V (0.92%)227.9 V3.5 V (1.52%)901.9 W✓ OK (≤3%)
400 mm²570 A445 A1.59 V (0.69%)228.4 V2.63 V (1.14%)676.4 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 35 Meter (230V)

Vilken kabelarea krävs för 425A vid 35 meter (230V)?

För 425 Ampere över 35 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.12V / 0.92%).

Hur stor effekt motsvarar 425A vid 230V?

Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.