Kabelarea för 425 Ampere vid 35 Meter (230V)
Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 35 m vid 230V.
Copper Cable (≤3% Drop)300 mm²Drop: 2.12V (0.92%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 2.63V (1.14%)
Voltage at Load227.9 VLine Loss: 901.9 W
Max Power & Breaker97.75 kW450A MCB/MCCB
IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 35m
| Cross-Section (mm²) | Cu Ampacity | Al Ampacity | Cu Voltage Drop | Load Voltage | Al Voltage Drop | Power Loss | Status |
|---|---|---|---|---|---|---|---|
| 1.5 mm² | 16 A | 12 A | 424.43 V (184.54%) | 0.0 V | 700.12 V (304.4%) | 180384.2 W | Drop High |
| 2.5 mm² | 24 A | 18 A | 254.66 V (110.72%) | 0.0 V | 420.07 V (182.64%) | 108230.5 W | Drop High |
| 4 mm² | 32 A | 25 A | 159.16 V (69.2%) | 70.8 V | 262.54 V (114.15%) | 67644.1 W | Drop High |
| 6 mm² | 41 A | 32 A | 106.11 V (46.13%) | 123.9 V | 175.03 V (76.1%) | 45096.0 W | Drop High |
| 10 mm² | 57 A | 44 A | 63.66 V (27.68%) | 166.3 V | 105.02 V (45.66%) | 27057.6 W | Drop High |
| 16 mm² | 76 A | 59 A | 39.79 V (17.3%) | 190.2 V | 65.64 V (28.54%) | 16911.0 W | Drop High |
| 25 mm² | 101 A | 78 A | 25.47 V (11.07%) | 204.5 V | 42.01 V (18.26%) | 10823.1 W | Drop High |
| 35 mm² | 125 A | 97 A | 18.19 V (7.91%) | 211.8 V | 30.0 V (13.05%) | 7730.8 W | Drop High |
| 50 mm² | 151 A | 118 A | 12.73 V (5.54%) | 217.3 V | 21.0 V (9.13%) | 5411.5 W | Drop High |
| 70 mm² | 192 A | 150 A | 9.09 V (3.95%) | 220.9 V | 15.0 V (6.52%) | 3865.4 W | Drop High |
| 95 mm² | 232 A | 181 A | 6.7 V (2.91%) | 223.3 V | 11.05 V (4.81%) | 2848.2 W | Drop High |
| 120 mm² | 269 A | 210 A | 5.31 V (2.31%) | 224.7 V | 8.75 V (3.8%) | 2254.8 W | Drop High |
| 150 mm² | 309 A | 241 A | 4.24 V (1.85%) | 225.8 V | 7.0 V (3.04%) | 1803.8 W | Drop High |
| 185 mm² | 353 A | 275 A | 3.44 V (1.5%) | 226.6 V | 5.68 V (2.47%) | 1462.6 W | Drop High |
| 240 mm² | 415 A | 324 A | 2.65 V (1.15%) | 227.3 V | 4.38 V (1.9%) | 1127.4 W | Drop High |
| 300 mm² | 477 A | 372 A | 2.12 V (0.92%) | 227.9 V | 3.5 V (1.52%) | 901.9 W | ✓ OK (≤3%) |
| 400 mm² | 570 A | 445 A | 1.59 V (0.69%) | 228.4 V | 2.63 V (1.14%) | 676.4 W | ✓ OK (≤3%) |
FAQ — Kabelarea för 425 Ampere vid 35 Meter (230V)
Vilken kabelarea krävs för 425A vid 35 meter (230V)?
För 425 Ampere över 35 meter vid 230V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (2.12V / 0.92%).
Hur stor effekt motsvarar 425A vid 230V?
Det motsvarar 97.75 kW med en rekommenderad säkring på 450A.
Related Lengths & Currents (230V)
425A · 5m (230V)425A · 10m (230V)425A · 15m (230V)425A · 20m (230V)425A · 25m (230V)425A · 30m (230V)425A · 40m (230V)425A · 45m (230V)425A · 50m (230V)425A · 60m (230V)425A · 70m (230V)10A · 35m (230V)16A · 35m (230V)20A · 35m (230V)25A · 35m (230V)32A · 35m (230V)40A · 35m (230V)50A · 35m (230V)63A · 35m (230V)80A · 35m (230V)100A · 35m (230V)125A · 35m (230V)160A · 35m (230V)200A · 35m (230V)